CODE SNIPPET
R609.6.2 Continuous Bond Beams Spanning Openings
Go To Full Code Chapter
R609.6.2.1
Under the provisions of this section, bond beams shall:
Notes:
Notes:
Notes:

- Be 16 inches (406 mm) high nominal over openings, except cast-in-place concrete bond beams, which may be 12 inches (305 mm) high nominal.
- Have top reinforcement continuous over the wall and opening.
- Have bottom reinforcement extending past each side of the opening a minimum of 24 inches (610 mm) for concrete walls and 4 inches (102 mm) for masonry walls.
- Meet the provisions of Tables R609.6.2.1(1), R609.6.2.1(2) and R609.6.2.1(3) as appropriate.
ROOF SPAN (FT) | MAXIMUM ALLOWABLE CLEAR SPAN (FT-IN)5 | |||||||||||
BOND BEAM 6" THICK WALL1, 2, 4 | BOND BEAM 8" THICK WALL1, 2, 4 | |||||||||||
16-1 | 16-2 | C12-1 | C12-2 | C16-1 | C16-2 | 16-1 | 16-2 | C12-1 | C12-2 | C16-1 | C16-2 | |
43 | 16-0 | 17-4 | 16-0 | 20-8 | 18-0 | 24-8 | 16-0 | 18-8 | 15-4 | 20-8 | 17-4 | 23-4 |
12 | 12-0 | 13-4 | 12-0 | 15-4 | 14-0 | 18-8 | 12-8 | 14-0 | 11-4 | 16-0 | 13-4 | 18-0 |
24 | 8-8 | 8-8 | 9-4 | 10-8 | 10-8 | 14-8 | 10-0 | 11-4 | 8-8 | 12-8 | 10-8 | 14-8 |
36 | 6-8 | 6-8 | 8-0 | 8-0 | 9-4 | 11-4 | 8-8 | 8-8 | 7-4 | 10-0 | 8-8 | 12-0 |
44 | 6-0 | 6-0 | 7-4 | 7-4 | 8-0 | 10-0 | 7-4 | 7-4 | 6-8 | 8-8 | 8-0 | 11-4 |
52 | 5-4 | 5-4 | 6-0 | 6-0 | 8-0 | 8-8 | 6-8 | 6-8 | 6-8 | 8-0 | 7-4 | 10-8 |
60 | 4-8 | 4-8 | 6-0 | 6-0 | 7-4 | 8-0 | 6-0 | 6-0 | 6-0 | 7-4 | 7-4 | 10-0 |
Notes:
- Designation of bond beam types over openings:
- Letter C designates a concrete bond beam. All other bond beams are masonry.
- The first number denotes the nominal height of the bond beam in inches.
- The second number denotes the number of No. 5 reinforcing bars in the top and the bottom of the beam. A single (1) No. 7 bar may be used in lieu of two No. 5 bars. The bottom reinforcing steel shall be located no more than 23/4-inches (70 mm) clear distance from the bottom of masonry bond beams and 11/2 inches (38 mm) for concrete bond beams.
- All bond beams have reinforcement in the top as required by Tables R609.2.2A-1 through 609.2.2A-4 and Tables R609.2.2B-1 through R609.2.2B-8 as appropriate. If two No.5 are required in this table and only one No.5 is required by Tables R609.2.2A-1 through R609.2.2A-4 and Tables R609.2.2B-1 through R609.2.2B-8 as appropriate, the additional bar shall be placed in the top of the bond beam over the opening and shall extend past the opening a minimum of 24 inches (610 mm).
- Use 4-foot (1219 mm) roof span for lintels in endwalls.
- The bottom reinforcement in precast lintels may be used to satisfy the continuous bond beam bottom reinforcement requirement.
- For roof dead loads more than 10 psf:
- For 20 psf roof dead load, multiply allowable clear spans by 0.85.
- For 30 psf roof dead load, multiply allowable clear spans by 0.75.
- Values for other roof dead loads may be interpolated.

BUILDING WIDTH (FT) | BOND BEAM 8" THICK WALL1, 2, 4 | ||||||
16-1 | 16-2 | C12-1 | C12-2 | C16-1 | C16-2 | C16-3 | |
MAXIMUM ALLOWABLE CLEAR SPAN (FT-IN)5 | |||||||
43 | 11-4 | 13-4 | 10-8 | 14-0 | 12-0 | 15-4 | 18-0 |
12 | 10-0 | 11-4 | 9-4 | 12-0 | 10-8 | 14-0 | 16-0 |
24 | 8-8 | 8-8 | 8-0 | 10-0 | 8-8 | 12-0 | 12-8 |
36 | 6-8 | 6-8 | 6-8 | 8-0 | 8-0 | 10-8 | 10-8 |
44 | 6-0 | 6-0 | 6-0 | 7-4 | 7-4 | 9-4 | 9-4 |
52 | 5-4 | 5-4 | 6-0 | 6-8 | 6-8 | 8-8 | 8-8 |
60 | 4-8 | 4-8 | 5-4 | 6-0 | 6-8 | 8-0 | 8-0 |
Notes:
- Designation of bond beam over openings:
- Letter C designates a concrete bond beam. All other bond beams are masonry.
- The first number denotes the nominal height of the bond beam in inches.
- The second number denotes the number of No. 5 reinforcing bars in the top and the bottom of the beam. One No. 7 may be used in lieu of two No. 5. The bottom reinforcing steel shall be located no more than 23/4-inches (70 mm) clear distance from the bottom of masonry bond beams and 11/2 inches (38 mm) for concrete bond beams.
- All bond beams shall have reinforcement in the top in accordance with Section R609.6.2.
- Use 4-foot (1219 mm) floor span for lintels in walls parallel to hollowcore.
- The bottom reinforcement in precast lintels may be used to satisfy the continuous bond beam bottom reinforcement requirement.
- This table is applicable for all roof dead loads.

BUILDING WIDTH (FT) | BOND BEAM 8" THICK WALL1, 2, 4 | ||||||
16-1 | 16-2 | C12-1 | C12-2 | C16-1 | C16-2 | C16-3 | |
MAXIMUM ALLOWABLE CLEAR SPAN (FT-IN)5 | |||||||
43 | 10-8 | 12-0 | 10-0 | 13-4 | 11-4 | 14-8 | 17-4 |
12 | 8-8 | 9-4 | 8-0 | 10-8 | 9-4 | 12-0 | 13-4 |
24 | 6-0 | 6-0 | 6-0 | 7-4 | 7-4 | 10-0 | 10-0 |
36 | 4-8 | 4-8 | 5-4 | 6-0 | 6-0 | 8-0 | 8-0 |
44 | 4-0 | 4-0 | 4-8 | 5-4 | 6-0 | 7-4 | 7-4 |
52 | 4-0 | 4-0 | 4-8 | 4-8 | 5-4 | 6-8 | 6-8 |
60 | 3-4 | 3-4 | 4-0 | 4-0 | 5-4 | 6-0 | 6-0 |
Notes:
- Designation of bond beam over openings:
- Letter C designates a concrete bond beam. All other bond beams are masonry.
- The first number denotes the nominal height of the bond beam in inches.
- The second number denotes the number of No. 5 reinforcing bars in the top and the bottom of the beam. One No. 7 may be used in lieu of two No. 5. The bottom reinforcing steel shall be located no more than 23/4-inches (70 mm) clear distance from the bottom of masonry bond beams and 11/2 inches (38 mm) for concrete bond beams.
- All bond beams shall have reinforcement in the top in accordance with Section R609.6.2.
- Use 4-foot (1219 mm) floor span for lintels in walls parallel to hollowcore.
- The bottom reinforcement in precast lintels may be used to satisfy the continuous bond beam bottom reinforcement requirement.
- This table is applicable for all roof dead loads.

R609.6.2.2
Top reinforcement required over the opening which is in addition to that required over the wall shall extend past the opening a minimum of 24 inches (610 mm).
Related Code Sections
R609.6.2 Wall Construction, Continuous Bond Beams Spanning Openings
of Tables R609.6.2.1(1), R609.6.2.1(2) and R609.6.2.1(3) as appropriate.
TABLE R609.6.2.1(1) MAXIMUM CLEAR SPAN CAPACITY OF CONTINUOUS BOND BEAMS ...
405.8 Buildings With Concrete or Masonry Exterior Walls, Assemblies and Beams Spanning Openings
extend a minimum of 24 inches (610 mm) past each side of the opening. Top bond beam reinforcement shall be continuous over wall and opening ...
R609.6.3.3 Wall Construction,
of the opening. Top bond beam reinforcement shall be continuous over wall and opening ...
R609.6.3 Wall Construction, Bond Beams Combined With Lintels
) COMBINED BOND BEAM/LINTELS ONE STORY AND TOP STORY OF MULTISTORY BUILDINGS
BOND BEAM HEIGHT (IN)
ROOF SPAN (FT)
MAXIMUM ALLOWABLE ...
405.8.1.3 Buildings With Concrete or Masonry Exterior Walls, Assemblies Used as a Bond Beam
Pre-engineered assemblies that are to be used as a bond beam over an opening shall comply with the following: 1. The bond beam reinforcement ...