CODE SNIPPET
R602.10.4.1 Continuous Sheathing Braced Wall Panels
Go To Full Code Chapter0
Continuous sheathing methods require structural panel sheathing to be used on all sheathable surfaces on one side of a braced wall line including areas above and below openings and gable end walls. Braced wall panels shall be constructed in accordance with one of the methods listed in Table R602.10.4.1. Different bracing methods, other than those listed in Table R602.10.4.1, shall not be permitted along a braced wall line with continuous sheathing.
METHOD | MATERIAL | MINIMUM THICKNESS | FIGURE | CONNECTION CRITERIA |
CS-WSP | Wood structural panel | 3/8" | 6d common (2" × 0.113") nails at 6" spacing (panel edges) and at 12" spacing (intermediate supports) or 16 ga. × 13/4 staples at 3" spacing (panel edges) and 6" spacing (intermediate supports) | |
CS-G | Wood structural panel adjacent to garage openings and supporting roof load onlya,b | 3/8" | See Method CS-WSP | |
CS-PF | Continuous portal frame | See Section R602.10.4.1.1 |
See Section R602.10.4.1.1 |
For SI: 1 inch = 25.4 mm, 1 pound per square foot = 47.89 Pa.
- Applies to one wall of a garage only.
- Roof covering dead loads shall be 3 psf or less.
R602.10.4.1.1 Continuous Portal Frame
Continuous portal frame braced wall panels shall be constructed in accordance with Figure R602.10.4.1.1. The number of continuous portal frame panels in a single braced wall line shall not exceed four. For purposes of resisting wind pressures acting perpendicular to the wall, the requirements of Figure R602.10.4.1.1 and Table R602.10.4.1.1 shall be met. There shall be a maximum of two braced wall segments per header and header length shall not exceed 22 feet (6706 mm). Tension straps shall be installed in accordance with the manufacturer's recommendations.
MINIMUM WALL STUD FRAMING NOMINAL SIZE AND GRADE | MAXIMUM PONY WALL HEIGHT (feet) | MAXIMUM TOTAL WALL HEIGHT (feet) |
MAXIMUM OPENING WIDTH (feet) |
BASIC WIND SPEED (mph) | |||||
85 | 90 | 100 | 85 | 90 | 100 | ||||
Exposure B | Exposure C | ||||||||
Tension strap capacity required (lbf)a,b | |||||||||
2 × 4 No. 2 Grade |
0 | 10 | 18 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 |
1 | 10 | 9 | 1000 | 1000 | 1000 | 1000 | 1000 | 1275 | |
16 | 1000 | 1000 | 1750 | 1800 | 2325 | 3500 | |||
18 | 1000 | 1200 | 2100 | 2175 | 2725 | DR | |||
2 | 10 | 9 | 1000 | 1000 | 1025 | 1075 | 1550 | 2500 | |
16 | 1525 | 2025 | 3125 | 3200 | 3900 | DR | |||
18 | 1875 | 2400 | 3575 | 3700 | DR | DR | |||
2 | 12 | 9 | 1000 | 1200 | 2075 | 2125 | 2750 | 4000 | |
16 | 2600 | 3200 | DR | DR | DR | DR | |||
18 | 3175 | 3850 | DR | DR | DR | DR | |||
4 | 12 | 9 | 1775 | 2350 | 3500 | 3550 | DR | DR | |
16 | 4175 | DR | DR | DR | DR | DR | |||
2 × 6 Stud Grade |
2 | 12 | 9 | 1000 | 1000 | 1325 | 1375 | 1750 | 2550 |
16 | 1650 | 2050 | 2925 | 3000 | 3550 | DR | |||
18 | 2025 | 2450 | 3425 | 3500 | 4100 | DR | |||
4 | 12 | 9 | 1125 | 1500 | 2225 | 2275 | 2775 | 3800 | |
16 | 2650 | 3150 | DR | DR | DR | DR | |||
18 | 3125 | 3675 | DR | DR | DR | DR |
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound force = 4.448 N.
- DR = design required.
- Strap shall be installed in accordance with manufacturer's recommendations.
Related Code Sections
R602.10.4.1 Wall Construction, Continuous Sheathing Braced Wall Panels
Continuous sheathing methods require structural panel sheathing to be used on all sheathable surfaces on one side of a braced wall line including ...
R602.10.4.3 Wall Construction, Length of Bracing for Continuous Sheathing
Braced wall lines with continuous sheathing shall be provided with braced wall panels in the length required in Tables R602.10.1.2(1) and R602.10.1.2 ...
R613.5.3 Wall Construction, Wall Bracing
SIP walls shall be braced in accordance with Section R602.10. SIP walls shall be considered continuous wood structural panel sheathing for purposes ...
R602.10.5.3 Wall Construction, Braced Wall Panel Location and Corner Construction
A braced wall panel shall be located at each end of a continuously-sheathed braced wall line. A minimum 32-inch (813 mm) structural fiberboard ...
R610.5.5 Wall Construction, Wall Bracing
SIP walls shall be braced in accordance with Section R602.10. SIP walls shall be considered continuous wood structural panel sheathing (bracing ...