Handrail gripping surfaces shall extend beyond and in the same direction of stair flights and ramp runs in accordance with 505.10.

EXCEPTIONS:
  1. Extensions shall not be required for continuous handrails at the inside turn of switchback or dogleg stairs and ramps.
  2. In assembly areas, extensions shall not be required for ramp handrails in aisles serving seating where the handrails are discontinuous to provide access to seating and to permit crossovers within aisles.
  3. In alterations, full extensions of handrails shall not be required where such extensions would be hazardous due to plan configuration.
505.10.1 Top and Bottom Extension at Ramps
Ramp handrails shall extend horizontally above the landing for 12 inches (305 mm) minimum beyond the top and bottom of ramp runs. Extensions shall return to a wall, guard, or the landing surface, or shall be continuous to the handrail of an adjacent ramp run.
Ramp handrails at the top and bottom are shown to extend horizontally above the landing 12 inches (305 mm) minimum from the ramp run. The extensions return to posts.
Top and Bottom Handrail Extension at Ramps
505.10.2 Top Extension at Stairs
At the top of a stair flight, handrails shall extend horizontally above the landing for 12 inches (305 mm) minimum beginning directly above the first riser nosing. Extensions shall return to a wall, guard, or the landing surface, or shall be continuous to the handrail of an adjacent stair flight.
The handrail extends horizontally above the landing for 12 inches (305 mm) minimum beginning directly above the first riser nosing.
Top Handrail Extension at Stairs
505.10.3 Bottom Extension at Stairs
At the bottom of a stair flight, handrails shall extend at the slope of the stair flight for a horizontal distance at least equal to one tread depth beyond the last riser nosing. Extension shall return to a wall, guard, or the landing surface, or shall be continuous to the handrail of an adjacent stair flight.
A handrail is shown to extend at the slope of the stair flight for a horizontal distance equal to one tread depth beyond the last riser nosing.
Bottom Handrail Extension at Stairs
UpCodes Diagrams

Related Code Sections

505.10 General Site and Building Elements, Handrail Extensions
, or the landing surface, or shall be continuous to the handrail of an adjacent ramp run. Figure 505.10.1 Top and Bottom Handrail Extension ...
1009.6.2 Recreation Facilities, Handrails
The width between handrails shall be 20 inches (510 mm) minimum and 24 inches (610 mm) maximum. Handrail extensions required by 505.10.3 shall ...
1008.2.5.3 Recreation Facilities, Handrails
: Handrails shall not be required on ramps located within ground level use zones. Handrail extensions shall not be required ...
1003.2.1 Recreation Facilities, Boat Slips
not be required. Where gangways and transition plates connect and are required to have handrails, handrail extensions shall not be required. Where handrail ...
505 General Site and Building Elements, Handrails
, or the landing surface, or shall be continuous to the handrail of an adjacent ramp run. Figure 505.10.1 Top and Bottom Handrail Extension ...