Center Break Isolator and double Break Isolator
The following documents were referred to during the preparation of this specification. In case of conflict, the provisions of this specification shall take precedence.
IEC 129:1975: Alternating Current Disconnectors (Isolators) and Earthing Switches
IEC 60694:2002: Common Specifications for High Voltage Switchgear and Controlgear
BS 729: Hot dip galvanized coating on iron and steel articles
IEC62271-102
Isolator (Disconnector) – a mechanical switching device which provides, in the open position, an isolating distance in accordance with Electrical Safety requirements.
SERVICE CONDITIONS
The isolator shall be suitable for continuous operation outdoors in tropical areas at altitudes of up to 2200m above sea level, humidities of up to 90%, average ambient temperature of +30ºC with a minimum of -1ºC and a maximum of +40ºC and heavy saline conditions along the coast.
4.2. DESIGN AND CONSTRUCTION
4.2.1 The Isolator, Solid Link shall be designed and constructed in accordance with IEC 129 and IEC 60694.
4.2.2 The isolating link shall be of the vertical opening, designed for single phase manual operation. It shall be easily removed and replaced by using a portable operating rod.
4.2.3 The isolating link shall incorporate double porcelain insulators to suit voltage requirements and mounted on hot dipped galvanised steel under base suitable for vertical mounting.
4.2.4 The isolating link shall be arranged so that each unit is mounted independently on an angle bracket. It shall be supplied complete with the angle bracket and accessories suitable for mounting on ‘U’ type steel channel. The drawings to be submitted shall indicate all the applicable mounting positions.
4.2.5 The isolator shall be designed such that in fully open position, it shall provide adequate electrical isolation between the contacts on each phase. It shall conform to the requirement as single point isolation for safety.
4.2.6 All steel parts shall be hot dip galvanized to BS 729. The minimum coating of galvanizing required is 80 microns.
4.2.7 The solid link shall be removable from the mounting by use of operating rod.
4.2.8 All current carrying parts of the isolator shall be made of high conductivity material.
4.2.9 The isolator shall be fitted with clamp connectors for Aluminium (ACSR) conductor of Aluminium (ACSR)conductor of up to 18.2mm diameter.
The rating of the complete isolator shall be as follows: –
Rated voltage
36 kV
Rated frequency
50 Hz
Rated lightning impulse withstand voltage
200 kV
Rated power frequency withstand voltage, dry
95 kV
Rated normal current
400 Amps
Rated short time withstand current for 3 sec, min.
18.0 kA
Minimum creepage distance of insulators
900 mm
N/O | DETAIL | DATA | ||
1 | Description | Solid link assembly complete with link rated at 200A and mounting bracket to PIESA 002. (See Figure 1 to Figure 12 below) |
||
2 | System conditions of service a) nominal Voltage (Un) r.m.s |
kV |
11 |
|
b) maximum system voltage (Um) r.m.s | KV | 12 | ||
c) earthing | Effective & non effective | |||
d) Frequency | Hz | 50 | ||
3 | Site conditions of service a) altitude |
m |
1400 |
|
b) Operating Ambient temperature | °C | –1 to 40 | ||
c) Humidity | % | 85 | ||
4 | Rating | |||
a) Nominal voltage | kV | 11 | ||
b) Rated current | Solid link | A |
200 |
|
Cut out base |
A |
200 |
||
5 | Electrical components | |||
a) Insulator material specification | Porcelain | |||
Dielectric strength | ||||
Lightning impulse withstand (1.2/50) | kV | 95 | ||
Power frequency wet withstand voltage r.m.s |
kV | 28 | ||
6 | Specific creepage distance | mm/kV | 25 |
7 | General information to be provided with bid: Drawings and brochures showing outline and general arrangement |
Yes/No |
Yes |
b) Detailed drawings of all items showing critical tolerances to be provided with bid |
Yes/No | Yes | |
8 | Previous Type test report/certificate on complete solid link assembly to be provided with bid |
Yes/No |
Yes |
10 | Routine tests (acceptance tests on sample Product) to be provided on delivery |
Yes/No | Yes |
11 | Applicable standard | PIESA 002 | |
12 | Other applicable standards | NRS 035 SABS IEC 60282–2 SABS IEC 60186 BS 137 part 2 |
TRI–LINKS
Lot 3–(a) 11kV with interrupters
N/O | DETAIL | DATA | |
1 | TYPE | 11kV pre-assembled gang operated overhead line load break switch complete with expulsion interrupters |
|
2 | Mounting configuration | Horizontal | |
3 | Mode of operation | Manually operated pole mounted linking rod and handle with locking facilities |
|
a) nominal Voltage (Un) r.m.s | kV | 11 | |
b) maximum voltage (Um) r.m.s | KV | 12 | |
c) earthing | Effective & non effective | ||
d) Frequency | Hz | 50 | |
e) rated current | Amp | 400 | |
f) Fault closing capacity | kA | 12.5 | |
4 | Site conditions of service a) altitude |
metres |
1400 |
b) Operating Ambient temperature | °C |
–1 to +40 |
|
c) Relative humidity | % | 85 | |
5 | Electrical components | ||
a) Insulator material specification | High Temperature Vulcanised Silicon rubber |
||
b) Cross arm and operating controls materials | Hot dip galvanized steel to SAN760 |
||
Dielectric strength | |||
Lightning impulse withstand (1.2/50) | kV | 95 |
Power frequency wet withstand voltage r.m.s | KV | 28 | |
Short time current rating –1sec | kA | 12.5 | |
6 | creepage distance | mm/kV | 25 |
7 | General information to be provided with bid: Drawings and brochures showing Outline and general arrangement |
Yes/No |
Yes |
8 | Previous Type test report/certificate on complete assembly to be provided with bid |
Yes/No | Yes. |
9 | Routine tests (acceptance tests on sample Product) to be provided on delivery. |
Yes/No | Yes |
10 | Applicable standards | IEC62271 |
FURTHER REQUIREMENTS:
Water shall not be able to accumulate on any part of the equipment nor shall any feature introduce moisture into any component.
The design shall incorporate all reasonable precautions and provisions for the safety of personnel concerned with the operation and maintenance of the same.
The current path shall be such that load current shall only flow through high conductive materials such as copper and its alloys. Load current shall not be permitted to flow through ferrous components, springs, or spring–loaded mechanisms.
All load current paths shall be so designed that the relevant parts of the switch are capable of carrying the specified rated current without exceeding the permitted temperature rise.
SUPPLIMENTARY NOTES
Suppliers should give sufficient information including drawings (which must be brief, clear and to the point) on how their switch designs addresses these requirements. Further, Suppliers may offer better alternatives that are of cost benefits to customer, It is therefore imperative that schedule "B" is completed by the tenderer. Any deviations/modifications/alternatives specification must be listed in schedule "C.
33kV with interrupters
N/O | DETAIL | DATA | |
1 | TYPE | 33kV pre-assembled gang operated overhead line load break switch complete with expulsion interrupters |
|
2 | Mounting configuration | Horizontal | |
3 | Mode of operation | Manually operated pole mounted linking rod and handle with locking facilities |
|
a) nominal Voltage (Un) r.m.s | kV | 33 | |
b) maximum voltage (Um) r.m.s | KV | 36 | |
c) earthing | Effective & non effective | ||
d) Frequency | Hz | 50 | |
e) rated current | Amp | 200 | |
f) Fault closing capacity | kA | 12.5 | |
4 | Site conditions of service a) altitude |
metres |
1400 |
b) Operating Ambient temperature | °C |
–1 to +40 |
|
c) Relative humidity | % | 85 | |
5 | Electrical components | ||
a) Insulator material specification | High Temperature Vulcanised Silicon rubber |
||
b) Cross arm and operating controls materials | Hot dip galvanized steel to SAN760 |
||
Dielectric strength | |||
Lightning impulse withstand (1.2/50) | kV | 170 | |
Power frequency wet withstand voltage r.m.s | KV | 70 | |
Short time current rating –1sec | kA | 12.5 | |
6 | creepage distance | mm/kV | 25 |
7 | General information to be provided with bid: |
Drawings and brochures showing Outline and general arrangement |
Yes/No |
Yes |
|
8 | Previous Type test report/certificate on complete assembly to be provided with bid |
Yes/No | Yes |
9 | Routine tests (acceptance tests on sample Product) to be provided on delivery |
Yes/No | Yes |
10 | Applicable standards | IEC62271 |
FURTHER REQUIREMENTS:
Water shall not be able to accumulate on any part of the equipment nor shall any feature introduce moisture into any component.
The design shall incorporate all reasonable precautions and provisions for the safety of personnel concerned with the operation and maintenance of the same.
The current path shall be such that load current shall only flow through high conductive materials such as copper and its alloys. Load current shall not be permitted to flow through ferrous components, springs, or spring–loaded mechanisms.
All load current paths shall be so designed that the relevant parts of the switch are capable of carrying the specified rated current without exceeding the permitted temperature rise.
SUPPLIMENTARY NOTES
Suppliers should give sufficient information including drawings (which must be brief, clear and to the point) on how their switch designs addresses these requirements. Further, Suppliers may offer better alternatives that are of cost benefits to custoemr.
11kV without interrupters
N/O | DETAIL | DATA | |
1 | TYPE | 11kV pre-assembled gang operated overhead line switch without expulsion interrupters (non–load break switch) |
|
2 | Mounting configuration | Horizontal | |
3 | Mode of operation | Manually operated pole mounted linking rod and handle with locking facilities |
|
a) nominal Voltage (Un) r.m.s | kV | 11 | |
b) maximum voltage (Um) r.m.s | KV | 12 | |
c) earthing | Effective & non effective | ||
d) Frequency | Hz | 50 | |
e) rated current | Amp | 400 | |
4 | Site conditions of service a) altitude |
metres |
1400 |
b) Operating Ambient temperature | °C |
–1 to +40 |
|
c) Relative humidity | % | 85 | |
5 | Electrical components | ||
a) Insulator material specification | High Temperature Vulcanised Silicon rubber |
||
b) Cross arm and operating controls materials | Hot dip galvanized steel to SAN760 |
||
Dielectric strength | |||
Lightning impulse withstand (1.2/50) | kV | 95 | |
Power frequency wet withstand voltage r.m.s | KV | 28 | |
Short time current rating –1sec | kA | 12.5 | |
6 | creepage distance | mm/kV | 25 |
7 | General information to be provided with bid: |
Drawing and brochures showing Outline and general arrangement |
Yes/No |
Yes |
|
8 | Previous Type test report/certificate on complete assembly to be provided with bid |
Yes/No | Yes |
9 | Routine tests (acceptance tests on sample Product) to be provided on delivery |
Yes/No | Yes |
10 | Applicable standards | IEC62271 |
FURTHER REQUIREMENTS:
Water shall not be able to accumulate on any part of the equipment nor shall any feature introduce moisture into any component.
The design shall incorporate all reasonable precautions and provisions for the safety of personnel concerned with the operation and maintenance of the same.
The current path shall be such that load current shall only flow through high conductive materials such as copper and its alloys. Load current shall not be permitted to flow through ferrous components, springs, or spring–loaded mechanisms.
All load current paths shall be so designed that the relevant parts of the switch are capable of carrying the specified rated current without exceeding the permitted temperature rise.
SUPPLIMENTARY NOTES
Suppliers should give sufficient information including drawings (which must be brief, clear and to the point) on how their switch designs addresses these requirements. Further, Suppliers may offer better alternatives that are of cost benefits to
33kV without interrupters
N/O | DETAIL | DATA | |
1 | TYPE | 33kV pre-assembled gang operated overhead line switch without expulsion interrupters (non–load break switch) |
|
2 | Mounting configuration | Horizontal | |
3 | Mode of operation | Manually operated pole mounted linking rod and handle with locking facilities |
|
a) nominal Voltage (Un) r.m.s | kV | 33 | |
b) maximum voltage (Um) r.m.s | KV | 36 | |
c) earthing | Effective & non effective | ||
d) Frequency | Hz | 50 | |
e) rated current | Amp | 200 | |
4 | Site conditions of service a) altitude |
metres |
1400 |
b) Operating Ambient temperature | °C |
–1 to +40 |
|
c) Relative humidity | % | 85 | |
5 | Electrical components | ||
a) Insulator material specification | High Temperature Vulcanised Silicon rubber |
||
b) Cross arm and operating controls materials | Hot dip galvanized steel to SAN760 |
||
Dielectric strength | |||
Lightning impulse withstand (1.2/50) | kV | 170 | |
Power frequency wet withstand voltage r.m.s | KV | 70 | |
Short time current rating –1sec | kA | 12.5 | |
6 | creepage distance | mm/kV | 25 |
7 | General information to be provided with bid: |
Drawing and brochures showing Outline and general arrangement |
Yes/No |
Yes |
|
8 | Previous Type test report/certificate on complete assembly to be provided with bid |
Yes/No | Yes |
9 | Routine tests (acceptance tests on sample Product) to be provided on delivery |
Yes/No | Yes |
10 | Applicable standards | IEC62271 |
FURTHER REQUIREMENTS:
Water shall not be able to accumulate on any part of the equipment nor shall any feature introduce moisture into any component.
The design shall incorporate all reasonable precautions and provisions for the safety of personnel concerned with the operation and maintenance of the same.
The current path shall be such that load current shall only flow through high conductive materials such as copper and its alloys. Load current shall not be permitted to flow through ferrous components, springs, or spring–loaded mechanisms.
All load current paths shall be so designed that the relevant parts of the switch are capable of carrying the specified rated current without exceeding the permitted temperature rise.
SUPPLIMENTARY NOTES
Suppliers should give sufficient information including drawings (which must be brief, clear and to the point) on how their switch designs addresses these requirements. Further, Suppliers may offer better alternatives that are of cost benefits to.
Recommended for You
Not exactly what you want?
Post Sourcing Request
Hot Searches
Time Switch
Level Switch
Industrial Switch
Manual Switch
Range Switch
We are China _DSC3526-1 manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular Disconnect Switch Products
15kv Outdoor Distribution Systems Disconnect Switch
Isolating Switch Electric Change Over Load Break Switch
Environmental Friendly Switchboard, Electric Switch, 27.5V Outdoor Switchgear for Transportation
High-Quality Outdoor High-Voltage Vacuum Circuit Breaker Fixed & Withdrawable Switch
Fuse Switch Disconnector Hr17b-160/30 160A 3p 11kv Fuse Type Isolating Switch
Popular Isolator Products
Hangzhou High Voltage Ceramics Drop out Fuse 33kv 24kv 11kv
T-Connectors Type Ty, Hydraulic Compression Type
Suspension Porcelain Insulator High Voltage Insulator U160blp
Polymeric 12kv 10ka Gapless Zinc Oxide Lightning Arrester with Mounting Bracket
Wholesale Electronics Electrical Fuse Cutout Switch 11kv
Popular jgtrade1 Products
Xgu-3 Suspension Clamp for ACSR Conducto
ED-2c, S80 Medium Voltage Porcelain Electric Shackle Insulator
10PCS Brushes Set 2*15mm 2*25mm 2*35mm 2*50mm 2*60mm
Fuse Cutout, Drop out Fuses 12kv 300A
Popular Switch Products
11kv Porcelain Insulator Fog Type Disc Suspension Ceramic Insulator
Sgld Series 380V Automatic Change-Over Switch (ATS) From 100A to 3200A
Switch, Hv Earthing Switch; Earthing Switch
33kv Disconnector Polymer Disconnect Switch
Hxgn1-12 Cubicle Fixed Indoor AC Metal-Clad Ring Main Unit Switchgear
Tags: Disconnect Switch, Isolator, jgtrade1, Switch