This Q & A is one of thousands posted in our Technical Expertise area, and answered on a daily basis by our Voltimum Experts.
Question: What reading should I be looking for when using earth rods on a construction site for a 1,600A mains? We are obviously using an RCD backup.
Some people say that it should 100 ohms; others say 200 ohms. Some even say 1 ohm – so what is your opinion?
Answer: In a TT installation, the value of earth resistance required for the main earth electrode depends on the required value for the primary protective device of the installation.
In BS 7671, in the case of where an RCD is fitted, reference should be made to Table 41.5 for a non-delayed RCD, and Table 3A for a Type S time delayed RCD.
BS 7430:2011, section 9.1 states that ‘this connection should have a resistance not greater than that required to operate the safety device’.
BS 7671, Table 41.5, Note 2 recommends that it should be as low as practical and a value above 200 ohms may not be stable.
Regulation 542.2.4 states that the earth electrode shall be such that soil drying and freezing will not increase its resistance above the required value.
To see many more Q & A in Voltimum UK's Experts Area, please click on the link. Experts from leading organisations provide online answers to your technical questions on a broad range of subjects. Our searchable database of existing Q & As now contains over 3,500 entries; you can browse through them here.
Links
-
Ask a question
You can ask a question of the Experts here
-
More Q&As of the Day (edited)
You can see many more edited Q & As of the Day in Voltimum UK's Experts Area