1. Introduction
The distributed energy resources connected to the electric power system (EPS) through voltage source converters (VSCs) are growing quickly [
1,
2,
3]. The ratio of synchronous generators (SGs) in traditional power systems decreases and the equivalent inertia of power grids is reduced. As a result, the system stability will be jeopardized [
4]. Moreover, the decrease of inertia will lead to a large frequency deviation and high rate of change of frequency (RoCoF) [
5,
6] under all kinds of disturbances to further damage the system. It is necessary to explore the control strategies that can equip the VSCs with inertia to overcome the adverse effects of low inertia.
Therefore, a variety of grid-forming control strategies for converters have been studied [
7]. The controls of virtual synchronous generators (VSGs) have been investigated, where the mature synchronous generator technology is embedded in the controller core and accordingly these converters have the dynamic behavior of conventional SGs. This has become popular in recent research [
8,
9,
10]. The characteristic comparison between VSG and SG is presented in
Table 1. As shown, VSGs have a more flexible coefficient design than SGs, which provide more of a design margin for the controller in VSGs. One way to control VSGs is through the synchronverter [
11], which can realize the astatic control of active and reactive power loops, making the system have the capacity for inertia provision and frequency and voltage regulations. More importantly, the electromagnetic characteristics of SGs are delicately inherited in synchronverters, including the dynamic behavior, which is more precise than other VSG types in portraying the electromagnetic dynamics performance. Moreover, phase-locked loop (PLL) control and the PLL-related instabilities in weak grid systems are avoided in synchronverters. In this case, the synchronverter is the competitive control for integrating RESs (Renewable Energy Sources), which are often located in remote areas and connected to a weak grid [
11], and also applied to high-voltage DC (HVDC) transmission systems with VSCs [
12]. Moreover, the weak grid will even lose more grid-strength with the large-scale access of power electronic devices, which will lead to the further reduction of inertia, damping, frequency/voltage regulation, and over-current capacity. The severe challenges to the safe and stable operation of power grids will be deeply imposed. In this situation, the advanced control technology with the active support ability of new energy exhibits important research value.
As one of the key stability problems of the power systems, angle stability can be divided into a small-signal and transient angle stability [
8,
9,
10,
11,
12,
13]. The small-signal analysis methods have been widely studied in VSG synchronverters by means of linear system theory such as eigenvalues and frequency analysis. The small-signal dynamics [
14,
15], the model establishment, and parameter design [
16,
17] of novel VSGs with optimized small-signal stability [
18,
19] are studied. Whereas, the analysis of transient angle stability is limited and needs to be further studied.
Firstly, the flexible and controllable parameters of the VSG body and power grid parameters will affect the transient stability. The virtual inertia and damping parameters of voltage-source VSGs, reactive droop coefficient, and line impedance parameters will affect the transient stability margin of the VSG itself. In this case, the research in [
20] analyzed the damping relationship of damping coefficient
D and inertial coefficient
J in the second-order transfer function with power angle. However, this method could not demonstrate the dynamics under different disturbances. Secondly, the transient stability of VSGs can be improved by using appropriate transient control strategy. For example, analog, with the classical analysis method of a transient problem in the traditional power system, Equal Area Law, the transient stability of VSGs can be converted into the Lyapunov energy function method. The VSG power-angle stability would be improved through “reducing the acceleration area and increasing the deceleration area”, as was representatively shown in [
21]. However, the Lyapunov energy function is not easy to obtain, and the prediction results always show some conservations. To improve the transient stability, some research studied the impact of the optimization of current limiting and the change of power reference or the limiting voltage on transient stability [
22,
23]. To simplify the analysis, the synchronizing coefficient is usually regarded as constant, then the equivalent synchronizing model was developed [
24]. However, the above methods are rarely used in synchronverters, whether in transient parameter or transient control designs. As mentioned, synchronverters have more precise descriptions of electromagnetic dynamics and weak PLL-dependence compared to other types of VSGs, which greatly benefits the active support capability of new energy. Therefore, it is valuable to investigate the stability improvement of synchronverters.
Synchronverters could remove the PLL to create self-synchronization and power synchronization control, in which the voltage source converter feature would be maintained during the switch between islanded and grid-connected modes [
25]. As a result, internal voltage dynamics can be used to demonstrate the essential characteristics of grid-connected VSGs whatever control strategies are applied. Some control methods based on the internal voltage stability of VSCs integrated into a weak grid are studied [
26,
27]. The effects of inner control on system stability based on internal voltage theory was revealed and a linearized model is derived in [
13]. However, these discussions have not given further insight into the physical mechanism of VSGs. Furthermore, the analysis needs to be extended into transient analysis so that the dynamics behavior can be comprehensively described.
Based on the conventional synchronous machine theory, electromagnetic behavior is used to describe the dynamics with the timescale covering the inductor and the capacitor characteristic in SGs. Due to the simulation of SG external characteristics in synchronverters, the equivalent motion dynamics of the synchronous generator rotor can also be applied. How to use the analysis method of SG rotor motion in the synchronverter is an interesting topic. According to SG theory, two unstable conditions in synchronverters can be described: (1) the virtual rotor angle is continuously increased due to the lack of synchronizing torque; (2) the virtual rotor will swing with the increasing amplitude due to the insufficient supply of damping torque.
In other words, the torque variance after suffering disturbance can be decomposed into two individual components:
where
Ts is the synchronous torque coefficient and
TD is the damping torque coefficient.
The stability of the power system is dependent on these two components of every power converter. Without sufficient synchronous torque, the virtual power angel and the rotor angle will be in an unstable operation with the phenomena of aperiodic deviation. On the other hand, the system will be led to unstable oscillation without enough damping torque. In this sense, the concepts of damping torque and synchronizing torque can be adopted in the synchronverter as well. In this paper, inspired by the SG theory, the concept of synchronverter internal voltage is proposed to describe the physical properties of a synchronverter with grid-connected operation mode. To explore the physical meaning, synchronverter inertia, damping torque, and synchronizing torque for low-frequency oscillation description are explained. In addition, how these torques influence the internal voltage stability is also discussed. In addition, to improve the transient dynamics, an auxiliary correction control loop across active power loop (APL) and reactive power loop (RPL) are proposed, which brings the positive effect on synchronverter transient stability without affecting the steady-state performances.
Contributions of this paper are as follows:
Considering the similarity of electromagnetic dynamics between synchronverters and SGs, the analysis method of internal voltage is proposed. Concepts of inertia, damping, and synchronizing torque in a wide timescale are presented, as well as the operation mechanism and transient modeling. It is the first time to apply the internal voltage method in VSGs. Therefore, synchronverters can be explored from the perspective of physical insight and mechanism explanation.
The auxiliary correction control loop linking APL and RPL is proposed, which helps to enhance transient robustness against varied disturbances. The biggest advantage of the proposed loop is its easy implementation.
The model and stability analysis method of synchronverters under varied disturbances are presented. Moreover, the effectiveness of the proposed correction control loop in transient improvement is analyzed.
This paper is organized as follows.
Section 2 introduces the preliminaries of synchronverters and describes the synchronverter control system.
Section 3 presents the modeling and concept of internal voltage. The concepts of inertia, damping torque, and synchronizing torque in electromechanical timescales are explained as well. The auxiliary correction control loop is proposed to improve the transient performance and is introduced in
Section 4. The model of synchronverters is established, the analysis under disturbances of different strength grids, and operating points is analyzed based on internal voltage theory. The impact of coefficients on the proposed correction loop is indicated as well. In
Section 5, simulation results are presented, and the conclusion is drawn in
Section 6.
2. Preliminaries
A synchronverter is a power electronic converter that mimics a conventional synchronous generator and acts as an interface for smart grid integration. As a result, distributed generation (DG) can easily take part in the frequency and voltage regulation and offer inertia and damping to the grid, as conventional synchronous generators do [
11]. A synchronverter consists of a power part and a control part. The controller of a three-phase synchronverter, as shown in
Figure 1, includes the mathematical model with a control core the same as a three-phase round-rotor synchronous machine. The back electromotive force
eg in the mathematical model is passed through a Pulse- Width Modulation (PWM) generation block to generate PWM signals to drive the power switches. The currents flowing out of the inductors are treated as the stator current
ig and feedback into the mathematical model. Two control loops, APL and RPL, are imbedded in the synchronverter controller.
Some assumptions are established: for a round rotor machine without damper windings, there are
p pairs of poles per phase and no saturation effects in the iron core, and no neutral line among stator windings to form a star topology. As shown, the synchronverter has two control loops, which are APL (
Figure 1a) and RPL (
Figure 1b).
APL mimics SG rotor dynamics and sometimes it does not need PLL (here, PLL is drawn in
Figure 1a for the grid-connected operation). The mechanical friction coefficient
Dp is equivalent to the frequency droop coefficient, which saves the design of an extra frequency droop loop. This loop can regulate the synchronverter frequency/speed
and generate the phase angle
for
eg.
Pt and
Qt are used to denote the active and reactive power injected into the grid from the PCC, respectively,
The electromechanics dynamics of the rotor is described as,
where
Jg is the moment of inertia of the rotational virtual rotor,
Tm is the mechanical torque, and
Te is the electromagnetic torque.
Dp is damping coefficient.
is the rotating speed of the synchronverter-emulated SG, and the equation related to the virtual rotor angle is represented by
.
is its reference value.
Te is obtained from the energy
E stored in the machine magnetic field:
where
denotes the excitation flux, and the mechanical torque is calculated by
.
Dp is defined as
(
), and it can be set for the torque to change 100% for a 1% frequency change, for example. The active torque
Tm can be obtained from the reference active power
Pref by dividing it with the nominal mechanical speed
[
11].
In RPL, as shown in
Figure 1b, the synchronverter output active power
Qg or line-to-line RMS value of the point of common coupling (PCC) terminal voltage
ut can be controlled by regulating the excitation flux
. The dynamics of
are descried as
where
Qref is the reference reactive power, which is equal to the nominal power here, and
and
are the line-to-line RMS value of reference and output terminal voltage, respectively. The difference between
and t
is amplified with the voltage droop coefficient
Dq before adding to the difference between
Qref and the reactive power
Qg. The resulting signal is then fed into an integrator with a gain of 1/
K to generate
. Here
K is dual to the inertia
Jg. The time constant
of the voltage loop is
In addition, there is,
Dq =
ΔQg/ΔUt. The active and reactive power are, respectively,
As shown in
Figure 1c, the synchronverter is connected to the grid with the voltage
. The inner voltage
eg of a synchronverter and its RMS value
Eg are addressed as,
The interface of a grid with a synchronverter needs to pass the output L-type filter with equivalent resistance
Rs and reactance
Xs. The PCC is connected to the grid via transmission line with resistance
Re and reactance
Xe. To simplify the analysis, the system is inductive dominant, which means
Xe > >
Re. Assuming that the phase angle of grid is
, an angle difference between the grid and synchronverter inner voltage will exist and is represented by
where
is the angular speed of the grid voltage, and
is the phase angle of
.
Note that is the line-to-line RMS value of .
According to the main circuit shown in
Figure 1, the relationship equation is obtained as follows:
3. Internal Voltage Analysis of Synchronverters
In a sense, synchronverters belong to the VSC category, which is inhered from VSC inner voltage characteristics but exhibits some differences.
3.1. Internal Voltage in Synchronverters
Figure 2 is the typical small-signal model of a single synchronous generator (SG) supplying an infinite bus system. In the torque-angle loop, the feedback electric torque Δ
Te is composed of two components, which can be expressed as:
If the circuit resistance is neglected, the coefficients
K1–
K4 in
Figure 2 are expressed as [
28]:
From the point of view of SG, the synchronverter has similar inner voltage characteristics theoretically. Following the conventional SG model, the synchronverter inner voltage can be defined as eg, which is located before the filter inductance. The angle is regarded as the power-angle. In a synchronverter, can be obtained through virtual mechanical dynamics, i.e., swing function.
Since
U∞ is the line-to-line RMS value of
u∞, according to the phase diagram shown in
Figure 3a, the RMS value of terminal voltage
ut is,
As for the transient dynamics of a synchronverter, control design could be implemented in different timescales.
3.2. Small-Signal Modeling of Synchronverter Internal Voltage
Some assumptions are established before the analysis of synchronverter small-signal modeling and are demonstrated as follows:
Control system dynamics in a fast current inner-loop timescale are neglected;
The effect of the AC capacitor is not considered;
The active power input Pin is constant.
As stated, the LCL filter is represented by the fundamental frequency impedance and the high-frequency component is shunted.
As shown in
Figure 1c, the grid interface of a synchronverter is closely linked with filter impedance and terminal impedance, as follows:
Equation (21) is organized by,
Equation (22) is written as,
Equation (1) is rewritten by combining (2):
Linearizing Equations (23) and (24), results in the following:
Based on equation (7), the linearized result is written:
In addition, linearization of the swing function (2) is obtained as follows:
As for the reactive power loop, the linearized function is represented by
3.3. Description of Inertia, Damping, and Synchronizing Torque
Synchronverters have some similar features with traditional synchronous generators. In this sense, the concepts of inertia, damping, and synchronizing torque can also be introduced in synchronverter analysis. Since the synchronverter is built by power electronic converters, the concepts of three different torque still exist during the operation.
The electromagnetic torque variation
is divided into two components, one is
and the other is
.
is used to describe damping torque in proportion to rotate speed
of the internal voltage, and
represents synchronizing torque which is in proportion to phase
. The equation characterizing the torque variation is addressed as follows:
where
H is the inertia coefficient of the synchronverter, Kd represents the damping torque coefficient, and Ks is the synchronizing torque coefficient.
Synchronverter damping torque and synchronizing torque are the main factors to keep systems stable and secure. As shown in
Figure 4, the small disturbance coming from the grid or load would produce variant torque, which is converted into variant synchronizing and damping torque. Due to the inheritance of a synchronous generator, the damping torque is directly proportional to the virtual damping coefficient
Dp, whereas synchronizing torque is affected by more factors. Synchronverters exchange damping torque with the grid, instead of consuming it through resistance, which is helpful to suppress oscillation of the rotation speed in the internal voltage. Synchronizing torque is applied to restrain the oscillation of the internal voltage phase, which is beneficial for the synchronization between the synchronverter and grid.
To investigate the impact of damping torque and synchronizing torque on the system stability in the synchronverter internal voltage, the small disturbance is forced and the movement trajectory of rotational phase and angular frequency variation is drawn, which is illustrated in
Figure 5 and built in the
-
reference frame. Although the synchronverter was enforced by disturbance, the phase and rotational speed variance of internal voltage will finally reach zero and the system will become stable. A phasor diagram of damping and synchronizing torque is shown in
Figure 5a, it is pointed out that the synchronizing torque is in phase with a small variation of synchronverter phase
. Whereas, the damping torque is in phase with the variation of synchronverter internal voltage rotational speed
as illustrated in Equations (31)–(33). The synthesized electromagnetic torque variation
is situated in the first quadrant under the damping and synchronizing torque actions, and thereby the small disturbance is restrained and even eliminated. Overall, the damping torque can be used to damp the oscillation of synchronverter rotational speed of internal voltage, and the synchronizing torque is contributed to damp the oscillation of internal voltage phase.
To investigate the impacts of the two torques on system stability, two cases are investigated, and the response results are illustrated in
Figure 6. It is clearly shown in
Figure 6a that the diverging oscillation of internal voltage occurs when damping torque is negative. On the other hand, the negative synchronizing torque (the damping power is still positive) will result in the synchronverter instability as shown in
Figure 6b. It is noteworthy that there is synchronizing torque to regulate by means of tuning
Ks in synchronverter, which indicates there is a possibility of PLL-less design that different with other VSC (voltage source converter) [
29]. Therefore, the internal voltage method provides an alternative for the mechanism-based analysis of the synchronverter.
The phasor diagram for demonstrating the leading effect of damping torque is illustrated in
Figure 7. Due to the leading effect, damping torque variant
is in the second quadrant. Compared with the normal condition, the synthesizing vectors
are more likely to step into the second quadrant to lose system stability when damping torque is reduced.
3.4. Proposed Synchronverter Controller Design
When disturbances such grid dip occur, the internal voltage of VSC in RPL is likely to oscillate and in turn deteriorate the APL stability. Since the droop coefficients in APL and RPL in synchronverters re hard to change due to the influence of steady-state droop characteristics, designing another auxiliary control loop would be a desirable method to improve the transient stability. In this paper, an auxiliary correction loop is proposed and added between APL and RPL, which is addressed by the red line in
Figure 8; the power interface with the grid is the same as
Figure 1 and neglected here. The input of the correction control loop is Ψ
f, and its output is obtained by the high-pass filtering of Ψ
f, where
Df is a tuneable parameter. The high-pass filter
can relieve the transient dynamics caused by the disturbances without changing the inertial characteristics in APL and RPL.
5. Simulation Results
To verify the validity of the internal voltage stability analysis method and results in
Section 4, a synchronverter system is built in SIMULINK/MATLAB. The specification of a synchronverter is shown in
Table 2. The internal voltage dynamics on different scenarios with variant disturbances are obtained.
Figure 16 illustrates the dynamics of synchronverter internal voltage with variant grid strengths. It can be observed that the disturbance from weak or stiff grids cannot influence the overall synchronverter stability. This phenomenon is in coordination with the analysis results described in
Figure 11 and
Figure 14, and phasor diagram in
Figure 16a–c. The dynamics of the internal voltage with changed active power outputs are shown in
Figure 17. The internal voltage has some oscillations under the different operating point
Pe. It restored more quickly when the synchronverter supplies less active power to the grid. The operation points have little impact on system stability, which is coordinated with the conclusions drawn from
Figure 9 and
Figure 12, phasor diagram of
Figure 15a,b. The results are different when the coefficient
Df is altered. The internal voltage is kept stable when
Df is positive and chosen as 3.5 and 0.1 and the dynamics response becomes a diverging oscillation when
Df is set as −1.5, which means the internal voltage is unstable. It reaches the conclusions obtained in
Figure 9 and
Figure 12. The phasor diagram is displayed in
Figure 18.
Figure 19 shows the waveforms of AC line voltage
ug, synchronverter output current
ig, and disturbances with switchovers among different operating points. It is demonstrated that the system is kept stable when the system is switched from 0 to operating points
Pe = 0.6 p. u., 1.0 p. u., and
Pe = 2.0 p. u. The oscillation during
Pe transition is almost neglected as shown in the results of the synchronverter current and voltage. It is validated that synchronverters have the robustness against disturbance of operating point changes, in which the results of internal voltage are similar to the results shown in
Figure 9a,
Figure 12a,
Figure 15a and
Figure 9b,
Figure 12b,
Figure 15b, respectively.
Figure 20 shows the results of AC line voltage
ug, synchronverter output current
ig, with disturbance having changed grid impedance in the condition of
Pe = 1.0 p. u. As shown, the simulation was carried out to realize SCR switching from the initial SCR = 3 to SCR = 15.4, 1.0, and 0.65 at the switch point,
t = 3 s, respectively. It is indicated that both overshoot and transient time in synchronverter current and voltage are small. It also reveals that internal voltage stability is weaker with the reduction of grid strength. Due to the introduction of extra damping and synchronizing torques imposed by synchronverters, the transient stability is still guaranteed in a wide range even when the synchronverter is suddenly connected to an extremely weak grid. It adheres to the analysis results shown in
Figure 11e,
Figure 14e,
Figure 15e and
Figure 11f,
Figure 14f,
Figure 15f, respectively.
Figure 21 illustrates responses of AC line voltage
ug, synchronverter output current
ig, and disturbance signal with different
Df in the condition of switching grid impedance from SCR = 3 to 0.65 at t = 3 s. As demonstrated in
Figure 20c, the transient stability of a synchronverter is influenced by the grid strength indicated by setting time and oscillation degree. We proposed an auxiliary correction control loop (shown in
Figure 8) to improve the transient dynamics without changing the steady-state performance. In contrast, the proposed control loop is added in a synchronverter with coefficient
Df = 3.5 in the condition similar to
Figure 20c. The results shown in
Figure 21a verify that the transient dynamics are much better after using the proposed correction loop. In other words, the proposed loop can dramatically improve the transient performance against some disturbances. However, inappropriate coefficient designs of
Df would jeopardize the transient stability or even lead to system collapse due to the insufficient damping or synchronizing torques. For example, the damping torque falls in the second quadrant to weaken the synthetic torque when
Df = −1.5. As a result, the synchronverter will lose its transient stability as shown in
Figure 21c. The simulation results coordinate with the results from
Figure 15c,d and
Figure 18. From a contrastive transient dynamics point of view, a synchronverter has more robustness against all kinds of disturbances than other conventional VSC.
6. Conclusions
This paper presents and develops the stability analysis method based on internal voltage stability for synchronverters. As opposed to SG, synchronverters have more control flexibility to change the transient dynamics. By contrast between synchronverters and SG, the similarity is identified. Accordingly, the concepts of inertia, damping torque, and synchronous torque are used to describe synchronverter internal voltage’s characteristics in electromechanical timescale. Through the analysis, synchronizing torque is in phase with the variance of internal voltage phase, used to synchronize the phase between the synchronverter and grid. Damping torque can damp the frequency oscillation. To investigate the internal voltage stability, phasor diagrams and Bode diagrams are analyzed. In addition, an auxiliary correction control loop across APL and RPL is proposed and added in the synchronverter control loop to enhance the robustness of synchronverters under disturbances. To verify the validity of the analysis method, the simulations are conducted, and the results are basically coordinated with the theoretical analysis. By using the method of internal voltage stability, the synchronverter can be explored from the perspective of physical insight and mechanism explanation, offering the novel idea in transient stability improvement.
From the perspective of practical application, synchronverters have been applied in many scenarios and projects in the world. The first and the largest scale of transformation for the main network project, Zhangbei wind-PV-storage base with an adjustment capacity of 547.5 MW, was built in 2016 and made a great contribution to the power supply of the 2022 Winter Olympics in Beijing. Compared with traditional synchronous generators, synchronverters are more effective in improving the new energy consumption capacity and its large-scale power supply conducted by new energy. A similar story is spreading to the UK, Germany, Ireland, etc. Synchronverter technique is gradually being incorporated into synchronous grid systems that accept a high proportion of new energy sources. The economic significance of this paper lies in the improvement and detailed theoretical analysis of the inverter-derived VSG control, so as to better respond to the cooperative design of the new energy carrier.