1. Introduction
In recent years, there has been a global push for a transition toward more environmentally friendly, low-carbon energy, with a focus on developing renewable energy sources such as solar energy, wind energy, and ocean energy. Solar energy in particular has attracted a lot of attention due to its clean, environmentally friendly nature, abundant reserves and ease of use [
1]. However, solar energy has inherent characteristics that result in high randomness and volatility of power generation. This volatility is exacerbated by the control characteristics of grid-connected PV systems. In addition, the use of nonlinear power electronic devices and maximum power point tracking (MPPT) algorithms lead to complex harmonic and interharmonic problems in the power system [
2]. These factors jointly affect the power quality of the system. The interharmonics are components with frequencies that are not integer multiples of the fundamental frequency.
Figure 1 illustrates the distribution of harmonic current and interharmonics in a grid-connected PV system [
3].
Compared to harmonics, interharmonics have a wider dispersion, pose more complex challenges to analysis, and carry greater risks. When interharmonic frequencies fall within the subsynchronous frequency band, they can interact with mechanical oscillations in neighboring generator shaft systems and cause subsynchronous oscillations that severely affect the stable operation of the power system [
4,
5,
6,
7]. An investigation of an incident in the United States involving damage to a turbine generator found that an interharmonic component at 55 Hz in the system current caused amplitude modulation of the 60 Hz fundamental wave, leading to the accident [
8]. Interharmonic waveform distortion can affect the proper operation of relay protection devices and cause malfunctions [
9]. The presence of low-frequency interharmonics with higher amplitudes can cause flickering in incandescent lamps and affect visual comfort [
10,
11,
12]. In addition, interharmonics reduce the power factor of the system and affect the quality of the grid-connected current.
With the increasing integration of grid-connected PV systems into the power grid, the interharmonic problem is becoming more pronounced. Therefore, it is of significant research importance and practical value to investigate the generation mechanism of interharmonics in grid-connected PV systems, understand their interharmonic output characteristics, and develop interharmonic suppression strategies to reduce the proportion of interharmonics in the output current of grid-connected PV systems.
In recent times, several researchers have investigated the generation mechanism and mathematical modelling of interharmonics in grid-connected PV systems. In [
13,
14,
15,
16], the generation mechanism of interharmonics was analyzed qualitatively based on experimental data. Pakonen et al. [
13] used experiments to demonstrate that the main cause of interharmonic current in grid-connected PV systems is the MPPT algorithm. Interestingly, the frequencies of the generated interharmonics are very close to the frequencies at which the human eye is most sensitive to changes in light brightness. Langella et al. [
14] also supports this view with experimental data, indicating that the interharmonic current caused by the MPPT algorithm is mainly concentrated in the frequency range from 0 to 100 Hz, while interharmonics with frequencies above 100 Hz can be neglected due to their low content. Furthermore, Langella et al. [
15] discussed whether the MPPT algorithm is the main source of interharmonics in grid-connected PV systems, and found that the relative magnitude of the interharmonic current is significantly influenced by the actual power. Sangwongwanich et al. [
16] explained in detail the process by which the MPPT algorithm generates interharmonics in grid-connected PV systems. They found that at the beginning of each MPPT cycle, the abrupt change in the DC voltage command issued by the MPPT results in a voltage error in the voltage loop, which is determined by the magnitude of the MPPT disturbance step. This error is then propagated through the controller to the current loop and ultimately results in the generation of interharmonic current due to modulation effects. These results contribute to a better understanding of the sources and characteristics of interharmonics in grid-connected PV systems, which can help in developing effective strategies to reduce their impact on power quality.
Building on the understanding of the interharmonic generation mechanism in grid-connected PV systems, a more comprehensive mathematical analysis of the interharmonic current was performed. In [
17], the interharmonic current in a grid-connected PV system was tested at different power levels and it was found that the power has no significant effect on the absolute magnitude of the interharmonic current. The study also determined the transfer function of a single-phase grid-connected inverter. Sangwongwanich et al. [
18] extended the scope of the study to the three-phase inverter and built a mathematical model of the interharmonic current in grid-connected PV systems, ignoring the dynamic characteristics of the current loop. The model showed that when the output frequency of the MPPT algorithm is f, the perturbation of the dc command results in an output current with a fundamental frequency of fg that contains an interharmonic component with a frequency of (fg ± f). Similarly, an interharmonic model for grid-connected PV systems based on dynamic phase perturbations was proposed [
19,
20], which reached the same conclusion. Mishra et al. [
21] proposed an improved integrated control strategy to reduce grid current harmonics and power ripples in a three-phase grid-connected photovoltaic (GTPV) system without a phase locked loop (PLL) unit. It was found that this only affects the amplitude of the interharmonic current, but not its frequency. Moreover, Jesus et al. [
22] proposed a mathematical model that links the compensation of harmonic currents to the oscillation of the capacitor voltage of the DC link. The conclusion is that all tested MPPT strategies face the problem of efficiency degradation due to harmonic current compensation. Overall, these mathematical analyses contribute to a deeper understanding of the interharmonic behaviour in grid-connected PV systems and provide valuable insights for developing effective strategies to mitigate and improve efficiency.
The main contributions of this paper are as follows:
(1) A transfer function approach is applied to establish a mathematical model, and the output characteristic equation of the PV array is linearized. The mathematical model of interharmonic current in PV grid-connected systems is built.
(2) A real-time calculation method of the amplitude of interharmonic current is introduced based on the established mathematical model.
(3) The output characteristics of interharmonic current are analyzed, and this paper investigates how different factors, such as MPPT parameters, main circuit parameters, and environmental factors, impact the interharmonic current.
(4) A series of simulation and experimental tests were designed to verify the effectiveness of the mathematical model for interharmonic currents.
The rest of the paper is arranged in following Sections.
Section 2 describes the mathematical model of interharmonic current.
Section 3 gives the real-time calculation method of the amplitude of interharmonic current.
Section 4 presents the detailed comparative analysis of interharmonic current characteristics. Finally, the conclusion of this paper is given in
Section 5.
2. The Current Situation of PV Technology on the Road
To develop the mathematical model of the inverter’s main circuit in a PV grid-connected system, the following system assumptions are made:
(1) Ignoring time delay and loss: the switch tube is treated as an ideal device, disregarding any time delay and losses that may occur during its turn-on and turn-off processes.
(2) Ideal AC side: the AC side is assumed to be an ideal three-phase symmetrical power grid.
(3) Ignoring inductor saturation: the saturation characteristics of the filter inductor are ignored.
The main circuit diagram of the inverter in the PV grid-connected system is illustrated in
Figure 2.
In
Figure 2,
ipv is the output current of the PV array;
vdc is DC voltage;
idc is DC current;
ia,
ib,
ic is the output current of the inverter;
ea,
eb,
ec are the grid voltages;
S1~
S6 are switch tubes;
Cdc is DC capacitor;
L is the filter inductance;
R is the line resistance; o is the DC side reference point of the inverter; n is the neutral point of the power grid.
After performing a simple formula derivation, the mathematical model of the PV grid-connected system inverter in a dq two-phase rotating coordinate system can be obtained as follows:
where the subscript d and q represent the d-axis and q-axis components of the corresponding physical quantities, respectively.
vd,
vq can be expressed as follows:
where
Sd,
Sq is the switching state in the dq coordinate system, which can be expressed as follows:
The common inverter controller is a voltage and current double closed-loop structure based on PI control, and its control block diagram is shown in
Figure 3.
In
Figure 3,
vdcref is the DC voltage command; and
idref,
iqref is the dq axis current command; in order to achieve the unit power factor,
iqref will be set to 0; and
vdref,
vqref for the dq axis voltage instruction. The outer voltage loop makes the DC voltage
vdc follow the command value
vdcref, the output of the voltage loop is used as the d-axis current command
idref, and the inner current loop makes the dq-axis current
id and
iq follow the command value
idref,
iqref, and output the dq-axis voltage command
vdref,
vqref. After the coordinate transformation, the drive signal is generated by PWM to the switch tube to complete the control of the inverter.
It can be seen from the model that the dq axis current is not only controlled by
vd and
vq, but also affected by the cross-coupling terms
ωLid and
ωLiq of the current. In order to eliminate the current coupling, the current inner loop adopts grid voltage feedforward and output filter inductor voltage decoupling control. The voltage control equation is as follows:
where
kip and
kii are the PI control parameters of the current loop.
Considering the sampling delay and PWM delay, the inverter can be equivalent to an inertial link with gain, and its transfer function can be expressed as the following:
where
KPWM is the bridge arm gain of the inverter;
Ts is the sampling period.
The PI controller transfer functions
Gv,
Gi and filter transfer function
Gfilter of the voltage loop and current loop are defined, respectively, as follows:
The transfer function of the d-axis output current to the d-axis output current command is as follows:
According to the voltage and current relationship of the capacitor, the DC capacitor
Cdc is analyzed as follows:
Ignoring the inverter loss, according to the instantaneous active power conservation relationship between the DC side and the AC side of the inverter, there is the following:
Thus, the relationship between the DC current and the d-axis current can be obtained as the following:
The transfer function block diagram of the PV grid-connected system is obtained, as shown in
Figure 4.
After tracking the maximum power point, the MPPT works into a steady state, and its output DC voltage command oscillates near the maximum power point voltage. Because the output current of the PV array has strong nonlinear characteristics, it is difficult to analyze. Therefore, it is linearized at the oscillation center, and the approximate value of the output current of the PV array is obtained as follows [
23]:
Next,
ipv0 is defined as the equivalent DC component of the output current of the PV array, and G is the equivalent output conductance of the PV array as follows [
23]:
Therefore, a simplified transfer function block diagram of the PV grid-connected system can be obtained, as shown in
Figure 5.
According to the simplified transfer function block diagram of the PV grid-connected system, the d-axis component of the output current is expressed as the following:
Defining
Gii as the transfer function of the d-axis component of the inverter output current to the equivalent DC component of the PV array output current, and
Giv as the transfer function of the d-axis component of the inverter output current to the MPPT output DC voltage instruction gives the following:
Next, the Fourier expansion of the three-point oscillating DC voltage instruction is as follows:
where
vn and
θn are the amplitude and phase angle of the Fourier expansion, respectively.
ωo = 2π/
To is the angular frequency of the three-point oscillation.
According to the frequency response characteristics of the linear system, under the action of the AC component in the MPPT output DC voltage command, the d-axis component of the inverter output current will contain the AC component of the corresponding frequency, namely, the following:
where
id0 is the DC component of the d-axis component of the output current.
idn and
θdn are the amplitude and phase angle of each frequency AC component in the d-axis component of the output current, respectively.
The amplitude of each frequency AC component in the d-axis component of the output current can be calculated according to the transfer function.
Under the unit power factor control, the q-axis component of the output current can be approximated as 0. The three-phase output current of the inverter can be obtained by inverse Park transformation of the output current in the dq coordinate system.
where the values of m for A, B, C three phases are 0, −1 and 1, respectively.
From Equations (16)–(19), we can see that when the DC voltage command of the MPPT output presents a three-point oscillation characteristic with an angular frequency of ωo, the output current of the PV grid-connected system will contain interharmonic components with angular frequencies of ωg − nωo and ωg + nωo (n = 1,3,5…). The amplitude of the interharmonic current at each frequency can be calculated by (18).
3. Real-Time Calculation Method of the Amplitude of Interharmonic Current
Through the mathematical model and characteristic analysis of the harmonic current between photovoltaic grid-connected systems, the frequency of the possible interharmonic current can be obtained, and its amplitude can be calculated for theoretical analysis. In order to effectively suppress the interharmonics of photovoltaic grid-connected systems, it is necessary to calculate the amplitude of the interharmonic current in the controller in real time. According to the orthogonality theorem of trigonometric functions [
24], the trigonometric functions formed by “1, sinx, cosx, sin2x, cos2x,… sinnx, cosnx” are orthogonal on the interval [−π, π], the integral of any two different functions on [−π, π] is 0, and then the integral of any two identical functions on [−π, π] is not 0, and is always equal to π.
The output current of a grid-connected PV system can be expressed as a superposition of countless sine waves. Taking phase A as an example, the output current
ia of the grid-connected PV system can be expressed as follows:
where
iaf is the fundamental wave component;
iai is the interharmonic component;
iah is the harmonic component.
The fundamental wave component
iaf can be calculated using the following:
where
Iaf_s is the amplitude of the sine component of the fundamental wave current;
Iaf_c is the amplitude of the cosine component of the fundamental wave current.
fg = 50 Hz, which is the power grid voltage frequency.
The interharmonic component
iai can be expressed as follows
where
and
are the amplitudes of sinusoidal components of interharmonic current whose frequencies are
fg-
nfo and
fg +
nfo, respectively;
and
are the amplitudes of cosine components of interharmonic currents whose frequencies are
fg −
nfo and
fg +
nfo, respectively.
fo is the three-point oscillation frequency of the DC voltage instruction output by MPPT.
And then, the harmonic component
iah can be expressed as follows:
where
Iahm_s is the amplitude of the sinusoidal component of the
m harmonic current, and
Iahm_c is the amplitude of the cosine component of the
m harmonic current.
Defining the interharmonic resolution frequency
fr and interharmonic resolution period
Tr:
where lcm(1/
fg,1/
fo) is the least common multiple of 1/
fg and 1/
fo.
The interharmonic resolution frequency
fr is exactly the resolution required for the Fourier analysis of waveforms consisting of fundamental waves of the frequency
fg, harmonics of the frequency
mfg, and interharmonics of the frequency
fg ±
nfo. The frequencies of the fundamental, harmonic and interharmonic components contained in current
ia are all integral multiples of
fr, and
ia can be reconstructed as the following:
where
is the amplitude of the sinusoidal component with frequency
kfr;
is the amplitude of the cosine component of frequency
kfr. These magnitudes are equal to the magnitudes of their corresponding interharmonic/fundamental/harmonic currents, respectively.
Obviously, the trigonometric functions that make up the current satisfy the orthogonality theorem, as follows
Replacing the integral variable with time
t, with the following:
Denoting
kfr as
fi, the amplitude of sinusoidal and cosine components of interharmonic current with frequency
fi can be calculated by the following:
For example, when the MPPT disturbance frequency
fmppt = 20 Hz, the three-point oscillation frequency
fo = 5 Hz of the DC voltage instruction, according to (24), the interharmonic resolution frequency
fr = 5 Hz. Thus, the A-phase output current can be expressed as follows:
The trigonometric function of the current satisfies the orthogonality theorem of trigonometric function on any interval of 0.2 s. According to (31), the amplitude of the sinusoidal component of the interharmonic current with a frequency of 15 Hz can be calculated as follows:
Based on the above analysis, the amplitude of sinusoidal and cosine components of harmonic currents between different frequencies can be calculated in real time.
6. Conclusions
Mathematical modeling and characteristic analysis of the interharmonic current in grid-connected PV systems was performed in this study.
The mathematical model of the interharmonic current was developed by deriving the transfer function of the grid-connected PV system. This was performed by linearizing the characteristic output equation of the PV generator at the point of maximum power.
An analysis of the characteristics of interharmonic currents in grid-connected PV systems was performed with the aid of the model, to investigate the distribution and amplitude characteristics of the interharmonics. The role of the main factors affecting the interharmonics, such as MPPT parameters, the main circuit parameters, and environmental conditions, was investigated.
Based on the above findings, strategies for suppressing interharmonics in grid-connected PV systems were proposed and tested. By understanding the interharmonic characteristics, these strategies can improve the power quality and stability of grid-connected systems.
A validation of the accuracy of the model and characteristic analysis was performed by means of simulations on MATLAB/Simulink and experiments on a low-power grid-connected PV system. The results from both methods confirmed the effectiveness of our proposed model and analysis.
The information regarding the behavior of interharmonic currents in grid-connected PV systems improves our understanding of how these currents are generated and distributed. This is useful for developing techniques to reduce them. By improving the performance and efficiency of grid-connected PV systems, these findings will be invaluable to industry.