The Non-Destructive Test of Steel Corrosion in Reinforced Concrete Bridges Using a Micro-Magnetic Sensor

1
College of Civil Engineering, Chongqing Jiaotong University, Chongqing 400074, China
2
School of Materials Science and Engineering, Chongqing Jiaotong University, Chongqing 400074, China
3
College of Civil Engineering, Chongqing Three Gorges University, Chongqing 404100, China
*
Author to whom correspondence should be addressed.
Sensors 2016, 16(9), 1439; https://doi.org/10.3390/s16091439
Submission received: 28 July 2016 / Revised: 30 August 2016 / Accepted: 2 September 2016 / Published: 6 September 2016
(This article belongs to the Section Physical Sensors)

Abstract

:
This paper presents a non-destructive test method for steel corrosion in reinforced concrete bridges by using a 3-dimensional digital micro-magnetic sensor to detect and analyze the self-magnetic field leakage from corroded reinforced concrete. The setup of the magnetic scanning device and the measurement mode of the micro-magnetic sensor are introduced. The numerical analysis model is also built based on the linear magnetic charge theory. Compared to the self-magnetic field leakage data obtained from magnetic sensor-based measurement and numerical calculation, it is shown that the curves of tangential magnetic field at different lift-off height all intersect near the edge of the steel corrosion zone. The result indicates that the intersection of magnetic field curves can be used to detect and evaluate the range of the inner steel corrosion in engineering structures. The findings of this work propose a new and effective non-destructive test method for steel corrosion, and therefore enlarge the application of the micro-magnetic sensor.

1. Introduction

Reinforced concrete is the most popular construction material in the world and widely used to bridge construction due to the advantage of strong bearing, low-cost, and easy construction. However, a major issue for reinforced concrete structures is the corrosion of the reinforcement steel bars exposed to aggressive environmental conditions, such as a humid, saline-alkaline climate. The steel corrosion makes a significant contribution to the failure of an engineering structure. Approximately 40% of damages of engineering structure result from the steel corrosion and there is a loss of ~14 billion dollars per year just in the United States. Therefore, the evaluation of corrosion in reinforced concrete is very important for the management and maintenance of engineering structures. The traditional nondestructive test techniques, such as electrochemical method [1], linear ultrasonic testing (UT) [2], eddy current testing (ECT) [3], infrared thermography (IRT) [4], and X-ray diffraction (XRD) [5], are all time-consuming technology or need expensive equipment for determining corrosion in the depth of reinforced concrete.
Reinforcing steel bars are made from a typical ferromagnetic material, which is a very important component of the reinforcing concrete structure. A defect (e.g., cracking, fatigue failure, stress concentration and corrosion) in ferromagnetic materials can change the structure of magnetic domains and their macro-properties are consequently changed, such as magnetoconductivity, coercive force, and hysteresis. This effect can be used for different applications in material science, especially in the field of nondestructive testing by using magnetic measurement to evaluate the status of the steel material in engineering structures, in particular to detect the stress-concentration, corrosion, and failure-originated zones. A number of nondestructive magnetic techniques have been developed, such as magnetic Barkhausen emission (MBE) [6], magnetoacoustic emission (MAE) [7], stress-induced magnetic anisotropy (SMA) [8], and magnetic field leakage (MFL) [9,10,11,12,13]. The physical mechanics of these techniques requires a strong magnetic field to magnetize the specimen for testing, and then detect induced-related phenomena to evaluate the health status of a specimen, so these techniques could be called active magnetic test methods. On the other hand, the shape and density of stimulated magnetic fields differ from the characteristic of tested objects. These techniques are time-consuming and even difficult to operate for some irregular structures [14]. For meeting the requirement of developing a more simple and effective magnetic technique in engineering, a positive magnetic method called metal magnetic memory (MMM) technique was proposed by A. A. Doubov in 1997 [15]. The advantage of MMM technique is that the Earth’s magnetic field instead of an artificial strong field is used as the stimulus source. Under the effect of the earth field and mechanical loads/defects, the self-magnetic field leakage (SMFL) signals are generated from corroded or stress-concentration regions where the tangential component reaches a maximum and the normal component transfers its polarity and has a zero value. The MMM technique is suitable for many engineering practices [16,17,18], but up to now has only been used as a qualitative test technique to determine the possible dangerous positions without quantitative results. The more accurate and quantitative criteria are deficient and required for the MMM technique.
In the present work, we introduce a passive magnetic test method to detect and evaluate the corrosion of reinforcement steel bars in the reinforced concrete structure by detecting the SMFL from the corrosion region. When a local corrosion happens, it brings a strong local corrosion pressure for expanding of corrosion products, which breaks the magnetic continuity and improves the magnetic resistivity of corrosion parts for the material loss and the magnetic-stress coupling [16,19]. The magnetic permeability is accordingly changed because of the stress-magnetic effect of iron as a ferromagnetic material. As a consequence, the SMFL is generated from the corrosion zone. By detecting and analyzing the SMFL signal produced by the corrosion, the position and status of corrosion in the reinforced concrete structure can be determined. This method does not need the equipment to actively excite a magnetic field, it is an effective, time-saving, and easy-operation method to non-destructively test the corrosion in the reinforced concrete structure.
The paper is organized as follows. In Section 2, the experimental setup and theoretical model based on the micro-magnetic sensor are introduced. The experimental results and calculated data of the SMFL signals are shown in Section 3, and the quantitative relationship between leaked magnetic field and steel corrosion is given. In Section 4, we summarize all these results.

2. Experimental Setup and Theoretical Model Based on Micro-Magnetic Sensor

2.1. Experiment Details Based on Micro-Magnetic Sensors

The corroded specimens of reinforced concrete are prepared by electrochemical method as shown in Figure 1. A steel bar is enwrapped by concrete, whose thickness T = 3 cm and the steel bar length L = 150 cm. The corrosion level can be controlled by the corroded current and time according to the Faraday law and the corrosion length can be controlled by the size of region infiltrated by electrolyte (5% NaCl solution).
Figure 2 shows the self-designed 3-dimensional (3D) scanning device for magnetic field measurement based on the 3D mechanical displacement system and the high-precision micro-magnetic sensor. The mechanical displacement system consists of 3D aluminum track and bracket system, stepping motor driver, and a hollow bar for supporting the sensor. The displacement accuracy of the stepping motor driver is as high as 0.1 mm. To improve the stability of the supporting bar when moving, a cable-stayed-like structure was used in the scanning device. The Honeywell HMR 2300 magnetometer is employed as the micro-magnetic sensor. It is a three-axis smart digital magnetometer, and the three axes oriented in orthogonal directions of HMR 2300 can measure the X, Y and Z vector components of a magnetic field. The output range of this micro-magnetic sensor is ±2 Gs with a resolution to less than 70 μGs.
Two reinforced concrete samples are corroded under a current intensity of 0.5 A and the corrosion time is 96 h, 120 h, and 144 h, respectively; while the corrosion length is ~20 cm and ~15 cm for the sample #1 and #2, respectively. The location and scanning paths of magnetic sensor imbedding on the 3D scanning device are shown in Figure 3, where the Hx component of magnetic field is defined as a tangential field. Figure 3 shows four scanning paths at different lift-off height (LFH) to scan the magnetic field around the reinforced concrete sample.

2.2. Theoretical Model for Measured Data

In order to establish a physical model for the SMFL signals from a corrosion region, a linear model considering the redistribution of magnetic charge in the corrosion zone is presented. Magnetic charge is an equivalent model, which has been developed to simulate the magnetic field leakage [20,21,22,23]. For a ferromagnet, its exterior magnetic field would be considered to originate from the magnetic charge: ρ = · M . M is the magnetization satisfying M = ( μ r 1 ) H mL , where μr is the relative magnetic permeability and HmL is the Weiss field which is the effective field producing self-magnetization in the ferromagnet. It is obvious that the quantity of charge is decided by the magnetization M, and then is only decided by μr when the Weiss field HmL is fixed. In other words, the magnetic charge is changed with the magnetic permeability of the material. For the steel bar under a local mechanical stress, the magnetic permeability would change due to the stress-magnetic effect. As a result, magnetic charge changes accordingly in these zones. For simplicity, here a phenomenological model is built in which a linear charge distribution is adopted.
As shown in Figure 4, we assume a defect with width 2b and depth h at the bar surface when the steel bar is partially lost due to the corrosion. Under the earth magnetic field, the dislocated magnetic charge is concentrated at both ends of the corrosion zone. Moreover, the corrosion induces a strong pressure stress on the steel bar and there exists a local stress concentration in the corrosion zone. For this reason, a redistribution of magnetic charge occurs at the bottom of the corrosion zone. The magnetic charge density in the corrosion zone can be expressed as
ρ ( x , y ) = { ρ max , ( x = b , h < y < 0 ) ρ max , ( x = b , h < y < 0 ) ρ max x b , ( b < x < b , y = h )
where ρmax denotes the maximum charge density, and the charge density is considered as the uniform distribution at the edges of the corroded region for simplicity.
As shown in Figure 5, the self-magnetic leakage field at a space point (x, y) generated by the charge elements of the three regions can be expressed by Equation (2), respectively.
d H 1 ( x , y ) = ρ ( x , y ) d y 2 π μ 0 r 1 2 r 1 d H 2 ( x , y ) = ρ ( x , y ) d y 2 π μ 0 r 2 2 r 2 d H 3 ( x , y ) = ρ ( x , y ) d x 2 π μ 0 r 3 2 r 3
where μ0 denotes the magnetic permeability in the air, r1, r2, and r3 denote the space vectors from the charge element to the space point, respectively.
Thus, the x and y components of total leaked magnetic field at space point (x, y) can be obtained by the integral of Equation (2). It can be expressed as
H x ( x , y ) = ρ max 2 π μ 0 ( arctan ( y + h x + b ) arctan ( y x + b ) ) ρ max 2 π μ 0 ( arctan y + h x b arctan y x b ) + ρ max 2 π μ 0 b ( 2 b ( y + h ) ( arctan b x y + h arctan b x y + h ) ) + ρ max 2 π μ 0 b ( x 2 ln ( b x ) 2 + ( y + h ) 2 ( b + x ) 2 + ( y + h ) 2 ) H y ( x , y ) = ρ max 4 π μ 0 ln ( x + b ) 2 + ( y + h ) 2 ( x + b ) 2 + y 2 ρ max 4 π μ 0 ln ( ( x b ) 2 + ( y + h ) 2 ( x b ) 2 + y 2 ) ρ max 2 π μ 0 b ( ( y + h ) 2 ln ( b x ) 2 + ( y + h ) 2 ( b + x ) 2 + ( y + h ) 2 ) ρ max 2 π μ 0 b ( x ( arctan b x y + h arctan b x y + h ) )

3. Results and Discussion for Steel Corrosion Based on Micro-Magnetic Sensor

First, we scanned the magnetic field around the two samples and obtained the tangential field (Hx) distributions as shown in Figure 6 and Figure 7, respectively. For the existence of demagnetization field of steel bar and the earth magnetic field, the Hx is nonzero, but the x-Hx curves at different LFH are almost parallel to each other for no damaged condition. There is no curve intersection, as shown in Figure 6a and Figure 7a, which is a typical Hx distribution for a healthy steel bar. Figure 6b–d plot the Hx dependent on the sensors position of sample #1 for the corrosion time of 96 h, 120 h, and 144 h, respectively. It is obvious that all the curves with different LFH intersect to two points when the samples are corroded. The distances between two intersecting points are 16.0 cm, 17.5 cm, and 18.5 cm for the different corrosion time, respectively. The longer the corrosion time is, the closer the distance is to the length of corrosion region. A similar result is found from the measurement for sample #2 for which curves are shown in Figure 7b–d. The result indicates that the position and regions of corrosion can be obtained by analyzing the SMFL signals outside of reinforced concrete.
For testing the real corroded area, the partial concrete has been removed to expose the corroded zone of the steel bar after magnetic detection. The morphology of the corrosion zone is shown in Figure 8. It can be found that the corrosion is actually not serious because the average corrosion depth is ~2 mm. Even the screw threads of the steel bar are not completely removed in the corroded zone. This means that the material removal is not the leading factor for the SMFL, but the corrosion pressure is.
For better understanding the experimental results, the tangential component Hx of self-magnetic leakage field outside of concrete can be determined according to Equation (3). Figure 9 shows the Hx distributions affected by the corrosion length (the value of 2b in the Figure 4). Clearly, the phenomena observed in the experiment have been captured in this model. The peaks of x-Hx exhibit the center of the corrosion region. Furthermore, it can be found that the x-Hx curves at different lift-off height (the value of y in Figure 5) all intersect at the same two points observed in the experiments. The distance Δx between the intersecting points is enlarged by increasing corrosion length and Δx almost equal to the corrosion length.

4. Conclusions

In this work, by detecting and analyzing the SMFL signals outside of corroded reinforced concrete using a micro-magnetic sensor, we find that the x-Hx curves obtained at different lift-off heights all intersect at the same points and the distances between intersecting points are basically equal to the length of the corrosion region. By a linear magnetic charge model, the distribution of Hx component is simulated and the intersection of curves is also found in the calculated results. This means that the corrosion improves the magnetic resistivity of the steel bar and produces magnetic charge concentration in the corrosion region, which generates this abnormal magnetic field distribution. The results propose a new magnetic NDT technique to detect and evaluate the inner corrosion in engineering structures using high-resolution micro-magnetic sensors. This method has many advantages over traditional techniques. It is a simple, inexpensive and efficient method to non-destructively test the corrosion in the reinforced concrete structure.

Acknowledgments

This work was supported by the National Science Fund for Distinguished Young Scholars (No. 51425801), the National Natural Science Foundation of China(Nos. 51278512, 51508058, 11404045), the Social livelihood science and technology innovation special of Chongqing (No. cstc2015shmszx30012 and No. cstc2015shmszx30029), the Science and Technology Project of Guizhou Provincial Transportation Department (No. 2016-123-006, 2016-123-039, 2016-123-040), the Science and Technology Planning Project of Yunnan Province (No. 2014 (A) 27), and the Communications Science and Technology Project of Guangxi Province of China (No. 20144805).

Author Contributions

J. Zhou arranged all the work in this project and gave a keen insight in this manuscript; H. Zhang and M. Yang performed the experiments; R. Zhao and R. Xia analyzed the measured data; L. Liao and R. Zhao carried out the simulation for the experimental results; H. Zhang and L. Liao wrote the manuscript.

Conflicts of Interest

The authors declare no conflict of interest.

References

  1. Lorenz, W.J.; Mansfeld, F. Determination of Corrosion Rates by Electrochemical DC and AC Methods. Corros. Sci. 1981, 21, 647–672. [Google Scholar] [CrossRef]
  2. Yeih, W.; Huang, R. Detection of the Corrosion Damage in Reinforced Concrete Members by Ultrasonic Testing. Cem. Concr. Res. 1998, 28, 1071–1083. [Google Scholar] [CrossRef]
  3. Tian, G.Y.; Rangarajan, S.; Sophian, A. Stress Measurement using Novel Eddy Current Probe. In Proceedings of the BINDT Annual Conference, Torquay, UK, 14–16 September 2004.
  4. Kobayashi, K.; Banthia, N. Corrosion Detection in Reinforced Concrete using Induction Heating and Infrared Thermography. J. Civil Struct. Health Monitor. 2011, 1, 25–35. [Google Scholar] [CrossRef]
  5. Suzuki, S.; Suzuki, S.; Matsubara, E.; Waseda, Y. In-situ X-ray Diffraction of Corrosion Products Formed on Iron Surfaces. Mater. Trans. 2005, 46, 637–662. [Google Scholar]
  6. Sakamoto, H.; Okada, M.; Homma, M. Theoretical Analysis of Barkhausen Noise in Carbon Steels. IEEE Trans. Magn. 1987, 23, 2236–2238. [Google Scholar] [CrossRef]
  7. Piotrowski, L.; Augustyniak, B.; Chmielewski, M.; Kowalewski, Z. Possibility of Application of Magnetoacoustic Emission for the Assessment of Plastic Deformation Level in Ferrous Materials. IEEE Trans. Magn. 2011, 47, 2087–2092. [Google Scholar] [CrossRef]
  8. Langman, R.A.; Mutton, P.J. Estimation of Residual Stresses in Railway Wheels by means of Stress-induced Magnetic Anisotropy. NDT E Inter. 1993, 26, 195–205. [Google Scholar] [CrossRef]
  9. Fitzgerald, C.S. Inspection for Rail Defects by Magnetic Induction. In Proceedings of the SPIE 2458 Nondestructive Evaluation of Aging Railroads, Oakland, CA, USA, 6 June 1995.
  10. Hall, D.R. Electromagnetic Inspection of Wire Ropes and strand-supported structures. Insight 2003, 45, 471–475. [Google Scholar] [CrossRef]
  11. Bergamini, A.; Christen, R. A Simple Approach to the Localization of Flaws in Large Diameter Steel Cables. In Proceedings of the SPIE 5047 Smart Nondestructive Evaluation and Health Monitoring of Structural and Biological Systems II, San Diego, CA, USA, 2 March 2003.
  12. Krieger, J.; Krause, H.J.; Gampe, U.; Sawade, G. Magnetic Field Measurements on Bridges and Development of a Mobile SQUID-System. In Proceedings of the SPIE 3587 Nondestructive Evaluation of Bridges and Highways III, Newport Beach, CA, USA, 3 March 1999.
  13. Xiong, E.G.; Wang, S.L.; Zhang, J.F.; Li, B. Magnetic Flux Leakage Testing Mechanism and Its Application. In Proceedings of the International Symposium on Innovation & Sustainability of Structures in Civil Engineering, Guangzhou, China, 29–30 November 2009.
  14. Wang, Z.D.; Gu, Y.; Wang, Y.S. A Review of Three Magnetic NDT Technologies. J. Magn. Magn. Mater. 2012, 324, 382–388. [Google Scholar] [CrossRef]
  15. Dubov, A.A. A Study of Metal Properties Using the Method of Magnetic Memory. Met. Sci. Heat Treat. 1997, 39, 401–405. [Google Scholar] [CrossRef]
  16. Shi, Y.; Zhang, C.; Li, R.; Cai, M.; Jia, G. Theory and Application of Magnetic Flux Leakage Pipeline Detection. Sensors 2015, 15, 31036–31055. [Google Scholar] [CrossRef] [PubMed]
  17. Han, W.H.; Shen, X.H.; Xu, J.; Wang, P.; Tian, G.Y.; Wu, Z.Y. Fast Estimation of Defect Profiles from the Magnetic Flux Leakage Signal Based on a Multi-Power Affine Projection Algorithm. Sensors 2014, 14, 16454–16466. [Google Scholar] [CrossRef] [PubMed]
  18. Yao, K.; Deng, B.; Wang, Z.D. Numerical Studies to Signal Characteristics with the Metal Magnetic Memory-effect in Plastically Deformed Samples. NDT E Inter. 2012, 47, 7–17. [Google Scholar] [CrossRef]
  19. Morón, C.; Cabrera, C.; Morón, A.; García, A.; González, M. Magnetic Sensors Based on Amorphous Ferromagnetic Materials: A Review. Sensors 2015, 15, 28340–28366. [Google Scholar] [CrossRef] [PubMed]
  20. Förster, F. Nondestructive Inspection by the Method of Magnetic Leakage Fields: Theoretical and Experimental Foundations of the Detection of Surface Cracks of Finite and Infinite Depth. Sov. J. Nondestr. Test 1982, 8, 841–859. [Google Scholar]
  21. Zatsepin, N.N.; Shcherbinin, V.E. Calculation of the Magnetostatic Field of Surface Defects I. Field to Pography of Defect Models. Sov. J. Nondestr. Test 1966, 5, 385–393. [Google Scholar]
  22. Shur, M.L.; Zagidulin, R.V.; Shcherbinin, V.E. Theoretical Problems of the Field Formation from a Surface Defect. Defektoskopiya 1988, 3, 14–25. (In Russian) [Google Scholar]
  23. Zagidulin, R.V. Calculation of the Remnant Magnetic Field of a Discontinuity Defect in a Ferromagnetic Sample. II. Remnant Magnetic Field of a Defect in the Air. Defektoskopiya 1998, 10, 33–39. (In Russian) [Google Scholar]
Figure 1. The schematic of electrochemical corrosion.
Figure 1. The schematic of electrochemical corrosion.
Sensors 16 01439 g001
Figure 2. The 3D scanning device for magnetic field measurement based on the micro-magnetic sensor. The inset shows the model of the micro-magnetic sensor.
Figure 2. The 3D scanning device for magnetic field measurement based on the micro-magnetic sensor. The inset shows the model of the micro-magnetic sensor.
Sensors 16 01439 g002
Figure 3. The location and scanning paths of the micro-magnetic sensor.
Figure 3. The location and scanning paths of the micro-magnetic sensor.
Sensors 16 01439 g003
Figure 4. The schematic of the magnetic charge distribution and corrosion pressure at the corrosion region on locally corroded steel bar enwrapped by concrete.
Figure 4. The schematic of the magnetic charge distribution and corrosion pressure at the corrosion region on locally corroded steel bar enwrapped by concrete.
Sensors 16 01439 g004
Figure 5. The self-magnetic leakage field generated from the magnetic charge at the corrosion region.
Figure 5. The self-magnetic leakage field generated from the magnetic charge at the corrosion region.
Sensors 16 01439 g005
Figure 6. The self-magnetic field around the sample #1 depends on the location of sensor at different lift-off height (LFH): (a) non-corroded; (b) corroded for 96 h; (c) corroded for 120 h; (d) corroded for 144 h.
Figure 6. The self-magnetic field around the sample #1 depends on the location of sensor at different lift-off height (LFH): (a) non-corroded; (b) corroded for 96 h; (c) corroded for 120 h; (d) corroded for 144 h.
Sensors 16 01439 g006
Figure 7. The self-magnetic field around the sample #2 depends on the location of sensor at different LFH: (a) non-corroded; (b) corroded for 96 h; (c) corroded for 120 h; (d) corroded for 144 h.
Figure 7. The self-magnetic field around the sample #2 depends on the location of sensor at different LFH: (a) non-corroded; (b) corroded for 96 h; (c) corroded for 120 h; (d) corroded for 144 h.
Sensors 16 01439 g007
Figure 8. The topography of corroded steel bar after removal of the cover concrete: (a) sample #1; (b) sample #2.
Figure 8. The topography of corroded steel bar after removal of the cover concrete: (a) sample #1; (b) sample #2.
Sensors 16 01439 g008
Figure 9. The calculated tangential Hx of self-magnetic leakage field at the different lift-off height (y = 2 cm, 4 cm, 6 cm) for the corrosion length 2b = 10 cm, 20 cm, 40 cm.
Figure 9. The calculated tangential Hx of self-magnetic leakage field at the different lift-off height (y = 2 cm, 4 cm, 6 cm) for the corrosion length 2b = 10 cm, 20 cm, 40 cm.
Sensors 16 01439 g009

Share and Cite

MDPI and ACS Style

Zhang, H.; Liao, L.; Zhao, R.; Zhou, J.; Yang, M.; Xia, R. The Non-Destructive Test of Steel Corrosion in Reinforced Concrete Bridges Using a Micro-Magnetic Sensor. Sensors 2016, 16, 1439. https://doi.org/10.3390/s16091439

AMA Style

Zhang H, Liao L, Zhao R, Zhou J, Yang M, Xia R. The Non-Destructive Test of Steel Corrosion in Reinforced Concrete Bridges Using a Micro-Magnetic Sensor. Sensors. 2016; 16(9):1439. https://doi.org/10.3390/s16091439

Chicago/Turabian Style

Zhang, Hong, Leng Liao, Ruiqiang Zhao, Jianting Zhou, Mao Yang, and Runchuan Xia. 2016. "The Non-Destructive Test of Steel Corrosion in Reinforced Concrete Bridges Using a Micro-Magnetic Sensor" Sensors 16, no. 9: 1439. https://doi.org/10.3390/s16091439

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop