Intelligent Ionization Smoke Detector
Intelligent Ionization Smoke Detector - pyramidtech.net
Intelligent Ionization Smoke Detector - pyramidtech.net
- No tags were found...
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
GE<br />
Security<br />
EST Fire & Life Safety<br />
<strong>Intelligent</strong> Initiating Devices<br />
Overview<br />
GE Security’s Signature Series Model SIGA-IS <strong>Intelligent</strong> <strong>Ionization</strong><br />
<strong>Smoke</strong> <strong>Detector</strong> gathers analog information from its smoke sensing<br />
element and converts it into digital signals. The detector’s on-board<br />
microprocessor measures and analyzes these signals. It compares<br />
the information to historical readings and time patterns to make<br />
an alarm decision. Digital filters remove signal patterns that are not<br />
typical of fires. Unwanted alarms are virtually eliminated.<br />
The microprocessor in each detector provides four additional benefits<br />
- Self-diagnostics and History Log, Automatic Device Mapping,<br />
Stand-alone Operation and Fast, Stable Communication.<br />
Self-diagnostics and History Log - Each Signature Series detector<br />
constantly runs self-checks to provide important maintenance<br />
information. The results of the self-check are automatically updated<br />
and permanently stored in the detector’s non-volatile memory<br />
Automatic Device Mapping - The loop controller learns where each<br />
device’s serial number address is installed relative to other devices<br />
on the circuit. The mapping feature provides supervision of each<br />
device’s installed location to prevent a detector from being reinstalled<br />
(after cleaning etc.) in a different location from where it was<br />
originally.<br />
Stand-alone Operation - A decentralized alarm decision by the<br />
detector is guaranteed. On-board intelligence permits the detector<br />
to operate in stand-alone mode. If loop controller CPU communications<br />
fail for more than four seconds, all devices on that circuit go<br />
into stand-alone mode. The circuit acts like a conventional alarm<br />
receiving circuit.<br />
Fast Stable Communication - On-board intelligence means less<br />
information needs to be sent between the detector and the loop<br />
controller. Other than regular supervisory polling response, the<br />
detector only needs to communicate with the loop controller when<br />
it has something new to report.<br />
Standard Features<br />
• Integral microprocessor<br />
• Non-volatile memory<br />
• Automatic device mapping<br />
• Electronic addressing<br />
• Environmental compensation<br />
• <strong>Intelligent</strong> detector<br />
• Wide 0.61% to 1.91%/ft. sensitivity range<br />
• Twenty pre-alarm sensitivity values, set in 5% increments¹<br />
• Identification of dirty or defective detectors<br />
• Automatic day/night sensitivity adjustment<br />
• Twin RED/GREEN status LEDs<br />
• Standard, relay, fault isolator, and audible mounting bases<br />
• Designed and manufactured to ISO 9001 standards<br />
Note: Some features described here may not be supported by all control systems.<br />
Check your control panel’s Installation and Operation Guide for details.<br />
<strong>Intelligent</strong><br />
<strong>Ionization</strong><br />
<strong>Smoke</strong> <strong>Detector</strong><br />
SIGA-IS<br />
S<br />
CHINA<br />
Application Notes<br />
Available<br />
Data Sheet 85001-0291 Issue 8<br />
Not to be used for installation purposes. Page of 4
Typical Wiring<br />
The detector mounting bases will accept #18 AWG (0.75mm 2 ), #16 (1.0mm 2 ), #14 AWG (1.5mm 2 ) and #12 AWG (2.5mm²) wire sizes.<br />
Note: Sizes #16 AWG (1.0mm 2 ) and #18 AWG (0.75mm 2 ) are preferred for ease of installation. See Signature Loop Controller catalog sheet for<br />
detailed wiring requirement specifications.<br />
Standard <strong>Detector</strong> Base, SIGA-SB, SIGA-SB4<br />
Term Description<br />
1 Not Used<br />
2 DATA IN/OUT (+)<br />
3 Not Used<br />
4 DATA IN (-)<br />
4 Remote LED (-)<br />
5 Remote LED (+)<br />
6 Not Used<br />
7 DATA OUT (-)<br />
Relay <strong>Detector</strong> Base, SIGA-RB, SIGA-RB4<br />
Term Description<br />
1 Normally-Open<br />
2 DATA IN/OUT (+)<br />
3 Common<br />
4 DATA IN (-)<br />
5 Not Used<br />
6 Normally-Closed<br />
7 DATA OUT (-)<br />
CONTACT RATING<br />
1.0 Amp @ 30 VDC<br />
(Pilot Duty)<br />
Isolator <strong>Detector</strong> Base, SIGA-IB, SIGA-IB4<br />
Audible <strong>Detector</strong> Base, SIGA-AB4G<br />
Term Description<br />
1 Not Used<br />
2 DATA IN/OUT (+)<br />
3 DATA IN (-)<br />
4 Not Used<br />
5 Not Used<br />
6 DATA OUT (-)<br />
7 Not Used<br />
Volume setting<br />
Default = High volume<br />
Cut for low volume<br />
SIG+<br />
DATA- DATA- DATA+<br />
SIG- OUT IN IN/OUT<br />
Tone setting<br />
Default = Temporal pattern<br />
Cut for steady tone<br />
To configure output volume<br />
or tone, cut the circuit board<br />
as shown.<br />
24 Vdc in<br />
From power supply or<br />
previous base<br />
-<br />
+<br />
-<br />
+<br />
24 Vdc out<br />
To next base or EOL relay<br />
Data in<br />
From Signature controller or<br />
previous device<br />
-<br />
+<br />
-<br />
+<br />
Data out<br />
To next Signature device<br />
Installation<br />
Signature Series detectors mount to North American 1-gang boxes,<br />
3-1/2 inch or 4 inch octagon boxes and to 4 inch square electrical<br />
boxes, 1-1/2 inches (38 mm) deep. They mount to European BESA<br />
and 1-gang boxes with 60.3 mm fixing centers.<br />
Testing & Maintenance<br />
Each detector automatically identifies when it is dirty or defective<br />
and causes a “dirty detector” message. The detector’s sensitivity<br />
measurement can also be transmitted to the loop controller. A<br />
sensitivity report can be printed to satisfy NFPA sensitivity measurements<br />
which must be conducted at the end of the first year and<br />
every two years thereafter.<br />
The user-friendly maintenance program shows the current state of<br />
each detector and other pertinent messages. Single detectors may<br />
be turned off temporarily, from the control panel. Availability of<br />
maintenance features is dependent on the fire alarm system used.<br />
Scheduled maintenance (Regular or Selected) for proper detector<br />
operation should be planned to meet the requirements of the Authority<br />
Having Jurisdiction (AHJ). Refer to current NFPA 72 and ULC<br />
CAN/ULC 536 standards.<br />
Compatibility<br />
The SIGA-IS detectors are compatible only with GE Security’s Signature<br />
Loop Controller.<br />
Data Sheet 85001-0291 Issue 8<br />
Not to be used for installation purposes. Page of 4
Application<br />
Although ionization detectors have a wide range of fire sensing capabilities they are best suited for detecting slow, smoldering fires. The<br />
table below shows six standard test fires used to rate the sensitivity of smoke and heat detectors. The table indicates that no single sensing<br />
element is suited for all test fires.<br />
GE Security recommends that this detector be installed according to latest recognized edition of national and local fire alarm codes.<br />
Test Fire SIGA-IS Ion SIGA-PS Photo<br />
SIGA-HRS and SIGA-<br />
HFS Rate-of-Rise/<br />
Fixed Temp.<br />
SIGA-PHS<br />
Photo Heat 3D<br />
SIGA-IPHS<br />
Ion/Photo/Heat 4D<br />
Open Wood optimum unsuitable optimum very suitable optimum<br />
Wood Pyrolysis suitable optimum unsuitable optimum optimum<br />
Smouldering Cotton very suitable optimum unsuitable optimum optimum<br />
Poly Urethane Foam very suitable very suitable suitable very suitable optimum<br />
n-Heptane optimum very suitable very suitable optimum optimum<br />
Liquid Fire without <strong>Smoke</strong> unsuitable unsuitable optimum very suitable very suitable<br />
Accessories<br />
All detector mounting bases have wiring terminals that are accessible<br />
from the “room-side” after mounting the base to the electrical<br />
box. The bases mount to North American 1-gang boxes and to 3½<br />
inch or 4 inch octagon boxes, 1½ inches (38 mm) deep. They also<br />
mount to European BESA and 1-gang boxes with 60.3 mm fixing<br />
centers. The SIGA-SB4, SIGA-RB4, and SIGA-IB4 mount to North<br />
American 4 inch square electrical boxes in addition to the above<br />
boxes. They include the SIGA-TS4 Trim Skirt which is used to cover<br />
the “mounting ears” on the base. The SIGA-AB4G mounts to a 4”<br />
sqare box only.<br />
SIGA-AB4G<br />
Audible Base<br />
SIGA-SB<br />
Standard Base<br />
SIGA-IB<br />
Isolator Base<br />
Standard Base SIGA-SB, SIGA-SB4 - This is the basic mounting base<br />
for GE Security Signature Series detectors. The SIGA-LED Remote<br />
LED is supported by the Standard Base.<br />
Relay Base SIGA-RB, SIGA-RB4 - This base includes a relay. Normally<br />
open or closed operation is selected during installation. The<br />
dry contact is rated for 1 amp (pilot duty) @ 30 Vdc. The relay’s<br />
position is supervised to avoid accidentally jarring it out of position.<br />
The SIGA-RB can be operated as a control relay if programmed to<br />
do so at the control panel (EST3 V. 2 only). The relay base does not<br />
support the SIGA-LED Remote LED.<br />
Audible Base SIGA-AB4G - This base is designed for use where<br />
localized or group alarm signaling is required. When the detector<br />
senses an alarm condition, the audible base emits a local alarm<br />
signal. The optional SIGA-CRR Polarity Reversal Relay can be used<br />
for sounding to other audible bases on the same 24 Vdc circuit.<br />
Relay and Audible Bases operate as follows:<br />
SIGA-RB<br />
Relay Base<br />
- at system power-up or reset, the relay is de-energized<br />
- when a detector is installed in the base with the power on,<br />
the relay energizes for four seconds, then de-energizes<br />
- when a detector is removed from a base with the power on,<br />
the relay is de-energized<br />
SIGA-LED<br />
Remote LED<br />
- when the detector enters the alarm state, the relay is energized.<br />
Isolator Base SIGA-IB, SIGA-IB4 - This base includes a built-in line<br />
fault isolator for use on Class A circuits. A detector must be installed<br />
for it to operate. The isolator base does not support the SIGA-LED<br />
Remote LED.<br />
The isolator operates as follows:<br />
- a short on the line causes all isolators to open within 23 msec<br />
- at 10 msec intervals, beginning on one side of the Class A<br />
circuit nearest the loop controller, the isolators close to<br />
provide the next isolator down the line with power<br />
- if the isolator next to the short closes, it reopens within 10 msec.<br />
The process repeats beginning on the other side of the loop controller.<br />
Remote LED SIGA-LED - The remote LED connects to the SIGA-SB<br />
or SIGA-SB4 Standard Base only. It features a North American size<br />
1-gang plastic faceplate with a white finish and red alarm LED.<br />
SIGA-TS4 Trim Skirt - Supplied with 4 inch bases, it can also be<br />
ordered separately to use with the other bases to help hide surface<br />
imperfections not covered by the smaller bases.<br />
Warnings & Cautions<br />
This detector will not operate without electrical power. As fires frequently<br />
cause power interruption, we suggest you discuss further<br />
safeguards with your fire protection specialist.<br />
This detector will NOT sense fires that start in areas where smoke<br />
cannot reach the detector. <strong>Smoke</strong> from fires in walls, roofs, or on the<br />
opposite side of closed doors may not reach the detector.<br />
This detector can be operated in environments where brief air velocity<br />
gusts of up to 300 ft per minute (1.52 m/s) are allowed.<br />
Data Sheet 85001-0291 Issue 8<br />
Not to be used for installation purposes. Page of 4
GE<br />
Security<br />
U.S.<br />
T 888-378-2329<br />
F 866-503-3996<br />
Canada<br />
T 519 376 2430<br />
F 519 376 7258<br />
Asia<br />
T 852 2907 8108<br />
F 852 2142 5063<br />
Australia<br />
T 61 3 9259 4700<br />
F 61 3 9259 4799<br />
Europe<br />
T 32 2 725 11 20<br />
F 32 2 721 86 13<br />
Latin America<br />
T 305 593 4301<br />
F 305 593 4300<br />
www.gesecurity.com<br />
© 2006 General Electric Company<br />
All Rights Reserved<br />
Signature Series is a Trademark<br />
of GE Security.<br />
Specifications<br />
Sensing Element <strong>Ionization</strong> - 1.0 µC Americium 241<br />
Air Velocity Range<br />
0 to 75 ft/min (0 to 0.38 m/s), (See Warnings and Cautions)<br />
Storage and Operating Operating Temp: 32ºF to 120ºF (0ºC to 49ºC)<br />
Environment<br />
Storage Temp: -4ºF to 140ºF (-20ºC to 60ºC)<br />
Humidity: 0 to 93% RH, Non-Condensing<br />
Altitude: 6,000 ft (1,828 m) maximum<br />
Sensitivity Range<br />
ULI / ULC - 0.61% to 1.91% obscuration/foot<br />
User Selected Alarm<br />
Most Sensitive: 0.7%/ft.; More Sensitive: 1.0% /ft. Normal: 1.2% /ft.<br />
Sensitivity Settings<br />
Less Sensitive: 1.4% /ft.; Least Sensitive: 1.6% /ft.<br />
Pre-alarm Sensitivity<br />
5% increments, allowing up to 20 pre-alarm settings<br />
Operating Voltage<br />
15.2 to 19.95 Vdc (19 Vdc nominal)<br />
Operating Current<br />
Quiescent: 45µA @ 19 V; Alarm: 45µA @ 19 V Emergency Standalone<br />
Alarm Mode: 18mA Pulse Current: 100 µA (100 msec) During<br />
Communication: 9 mA maximum<br />
Construction & Finish High Impact Engineering Polymer - White<br />
Compatible Mounting Bases SIGA-SB Standard Base, SIGA-RB Relay Base, SIGA-IB Isolator Base,<br />
SIGA-AB4, SIGA-AB4G Audible Bases<br />
LED Operation<br />
On-board Green LED - Flashes when polled On-board Red LED<br />
- Flashes when in alarm Both LEDs - Glow steady when in alarm<br />
(stand-alone) Compatible Remote Red LED SIGA-LED Flashes when<br />
in alarm<br />
Compatibility<br />
Use With: SIGNATURE Loop Controller<br />
Address Requirements Uses one Device Address<br />
UL Listed Spacing<br />
30 ft<br />
Agency Listings<br />
UL, ULC, MEA, CSFM<br />
Ordering Information<br />
Catalog Description<br />
Ship Wt.<br />
Number<br />
lbs (kg)<br />
SIGA-IS <strong>Intelligent</strong> <strong>Ionization</strong> <strong>Detector</strong> - UL/ULC Listed 0.5 (.23)<br />
Accessories<br />
SIGA-SB <strong>Detector</strong> Mounting Base - Standard<br />
SIGA-SB4 4 inch <strong>Detector</strong> Mounting Base c/w SIGA-TS4 Trim Skirt<br />
SIGA-RB <strong>Detector</strong> Mounting Base w/Relay<br />
0.2 (.09)<br />
SIGA-RB4 4 inch <strong>Detector</strong> Mounting Base w/Relay c/w SIGA-TS4 Trim Skirt<br />
SIGA-IB <strong>Detector</strong> Mounting Base w/Fault Isolator<br />
SIGA-IB4 4 inch <strong>Detector</strong> Mounting Base w/Fault Isolator<br />
and SIGA-TS4 Trim Skirt<br />
0.1 (.04)<br />
SIGA-AB4G Audible (Sounder) Base 0.1 (.04)<br />
Data Sheet 85001-0291 Issue 8<br />
Not to be used for installation purposes. Page of 4