09.09.2015 Views

Intelligent Ionization Smoke Detector

Intelligent Ionization Smoke Detector - pyramidtech.net

Intelligent Ionization Smoke Detector - pyramidtech.net

SHOW MORE
SHOW LESS
  • No tags were found...

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

GE<br />

Security<br />

EST Fire & Life Safety<br />

<strong>Intelligent</strong> Initiating Devices<br />

Overview<br />

GE Security’s Signature Series Model SIGA-IS <strong>Intelligent</strong> <strong>Ionization</strong><br />

<strong>Smoke</strong> <strong>Detector</strong> gathers analog information from its smoke sensing<br />

element and converts it into digital signals. The detector’s on-board<br />

microprocessor measures and analyzes these signals. It compares<br />

the information to historical readings and time patterns to make<br />

an alarm decision. Digital filters remove signal patterns that are not<br />

typical of fires. Unwanted alarms are virtually eliminated.<br />

The microprocessor in each detector provides four additional benefits<br />

- Self-diagnostics and History Log, Automatic Device Mapping,<br />

Stand-alone Operation and Fast, Stable Communication.<br />

Self-diagnostics and History Log - Each Signature Series detector<br />

constantly runs self-checks to provide important maintenance<br />

information. The results of the self-check are automatically updated<br />

and permanently stored in the detector’s non-volatile memory<br />

Automatic Device Mapping - The loop controller learns where each<br />

device’s serial number address is installed relative to other devices<br />

on the circuit. The mapping feature provides supervision of each<br />

device’s installed location to prevent a detector from being reinstalled<br />

(after cleaning etc.) in a different location from where it was<br />

originally.<br />

Stand-alone Operation - A decentralized alarm decision by the<br />

detector is guaranteed. On-board intelligence permits the detector<br />

to operate in stand-alone mode. If loop controller CPU communications<br />

fail for more than four seconds, all devices on that circuit go<br />

into stand-alone mode. The circuit acts like a conventional alarm<br />

receiving circuit.<br />

Fast Stable Communication - On-board intelligence means less<br />

information needs to be sent between the detector and the loop<br />

controller. Other than regular supervisory polling response, the<br />

detector only needs to communicate with the loop controller when<br />

it has something new to report.<br />

Standard Features<br />

• Integral microprocessor<br />

• Non-volatile memory<br />

• Automatic device mapping<br />

• Electronic addressing<br />

• Environmental compensation<br />

• <strong>Intelligent</strong> detector<br />

• Wide 0.61% to 1.91%/ft. sensitivity range<br />

• Twenty pre-alarm sensitivity values, set in 5% increments¹<br />

• Identification of dirty or defective detectors<br />

• Automatic day/night sensitivity adjustment<br />

• Twin RED/GREEN status LEDs<br />

• Standard, relay, fault isolator, and audible mounting bases<br />

• Designed and manufactured to ISO 9001 standards<br />

Note: Some features described here may not be supported by all control systems.<br />

Check your control panel’s Installation and Operation Guide for details.<br />

<strong>Intelligent</strong><br />

<strong>Ionization</strong><br />

<strong>Smoke</strong> <strong>Detector</strong><br />

SIGA-IS<br />

S<br />

CHINA<br />

Application Notes<br />

Available<br />

Data Sheet 85001-0291 Issue 8<br />

Not to be used for installation purposes. Page of 4


Typical Wiring<br />

The detector mounting bases will accept #18 AWG (0.75mm 2 ), #16 (1.0mm 2 ), #14 AWG (1.5mm 2 ) and #12 AWG (2.5mm²) wire sizes.<br />

Note: Sizes #16 AWG (1.0mm 2 ) and #18 AWG (0.75mm 2 ) are preferred for ease of installation. See Signature Loop Controller catalog sheet for<br />

detailed wiring requirement specifications.<br />

Standard <strong>Detector</strong> Base, SIGA-SB, SIGA-SB4<br />

Term Description<br />

1 Not Used<br />

2 DATA IN/OUT (+)<br />

3 Not Used<br />

4 DATA IN (-)<br />

4 Remote LED (-)<br />

5 Remote LED (+)<br />

6 Not Used<br />

7 DATA OUT (-)<br />

Relay <strong>Detector</strong> Base, SIGA-RB, SIGA-RB4<br />

Term Description<br />

1 Normally-Open<br />

2 DATA IN/OUT (+)<br />

3 Common<br />

4 DATA IN (-)<br />

5 Not Used<br />

6 Normally-Closed<br />

7 DATA OUT (-)<br />

CONTACT RATING<br />

1.0 Amp @ 30 VDC<br />

(Pilot Duty)<br />

Isolator <strong>Detector</strong> Base, SIGA-IB, SIGA-IB4<br />

Audible <strong>Detector</strong> Base, SIGA-AB4G<br />

Term Description<br />

1 Not Used<br />

2 DATA IN/OUT (+)<br />

3 DATA IN (-)<br />

4 Not Used<br />

5 Not Used<br />

6 DATA OUT (-)<br />

7 Not Used<br />

Volume setting<br />

Default = High volume<br />

Cut for low volume<br />

SIG+<br />

DATA- DATA- DATA+<br />

SIG- OUT IN IN/OUT<br />

Tone setting<br />

Default = Temporal pattern<br />

Cut for steady tone<br />

To configure output volume<br />

or tone, cut the circuit board<br />

as shown.<br />

24 Vdc in<br />

From power supply or<br />

previous base<br />

-<br />

+<br />

-<br />

+<br />

24 Vdc out<br />

To next base or EOL relay<br />

Data in<br />

From Signature controller or<br />

previous device<br />

-<br />

+<br />

-<br />

+<br />

Data out<br />

To next Signature device<br />

Installation<br />

Signature Series detectors mount to North American 1-gang boxes,<br />

3-1/2 inch or 4 inch octagon boxes and to 4 inch square electrical<br />

boxes, 1-1/2 inches (38 mm) deep. They mount to European BESA<br />

and 1-gang boxes with 60.3 mm fixing centers.<br />

Testing & Maintenance<br />

Each detector automatically identifies when it is dirty or defective<br />

and causes a “dirty detector” message. The detector’s sensitivity<br />

measurement can also be transmitted to the loop controller. A<br />

sensitivity report can be printed to satisfy NFPA sensitivity measurements<br />

which must be conducted at the end of the first year and<br />

every two years thereafter.<br />

The user-friendly maintenance program shows the current state of<br />

each detector and other pertinent messages. Single detectors may<br />

be turned off temporarily, from the control panel. Availability of<br />

maintenance features is dependent on the fire alarm system used.<br />

Scheduled maintenance (Regular or Selected) for proper detector<br />

operation should be planned to meet the requirements of the Authority<br />

Having Jurisdiction (AHJ). Refer to current NFPA 72 and ULC<br />

CAN/ULC 536 standards.<br />

Compatibility<br />

The SIGA-IS detectors are compatible only with GE Security’s Signature<br />

Loop Controller.<br />

Data Sheet 85001-0291 Issue 8<br />

Not to be used for installation purposes. Page of 4


Application<br />

Although ionization detectors have a wide range of fire sensing capabilities they are best suited for detecting slow, smoldering fires. The<br />

table below shows six standard test fires used to rate the sensitivity of smoke and heat detectors. The table indicates that no single sensing<br />

element is suited for all test fires.<br />

GE Security recommends that this detector be installed according to latest recognized edition of national and local fire alarm codes.<br />

Test Fire SIGA-IS Ion SIGA-PS Photo<br />

SIGA-HRS and SIGA-<br />

HFS Rate-of-Rise/<br />

Fixed Temp.<br />

SIGA-PHS<br />

Photo Heat 3D<br />

SIGA-IPHS<br />

Ion/Photo/Heat 4D<br />

Open Wood optimum unsuitable optimum very suitable optimum<br />

Wood Pyrolysis suitable optimum unsuitable optimum optimum<br />

Smouldering Cotton very suitable optimum unsuitable optimum optimum<br />

Poly Urethane Foam very suitable very suitable suitable very suitable optimum<br />

n-Heptane optimum very suitable very suitable optimum optimum<br />

Liquid Fire without <strong>Smoke</strong> unsuitable unsuitable optimum very suitable very suitable<br />

Accessories<br />

All detector mounting bases have wiring terminals that are accessible<br />

from the “room-side” after mounting the base to the electrical<br />

box. The bases mount to North American 1-gang boxes and to 3½<br />

inch or 4 inch octagon boxes, 1½ inches (38 mm) deep. They also<br />

mount to European BESA and 1-gang boxes with 60.3 mm fixing<br />

centers. The SIGA-SB4, SIGA-RB4, and SIGA-IB4 mount to North<br />

American 4 inch square electrical boxes in addition to the above<br />

boxes. They include the SIGA-TS4 Trim Skirt which is used to cover<br />

the “mounting ears” on the base. The SIGA-AB4G mounts to a 4”<br />

sqare box only.<br />

SIGA-AB4G<br />

Audible Base<br />

SIGA-SB<br />

Standard Base<br />

SIGA-IB<br />

Isolator Base<br />

Standard Base SIGA-SB, SIGA-SB4 - This is the basic mounting base<br />

for GE Security Signature Series detectors. The SIGA-LED Remote<br />

LED is supported by the Standard Base.<br />

Relay Base SIGA-RB, SIGA-RB4 - This base includes a relay. Normally<br />

open or closed operation is selected during installation. The<br />

dry contact is rated for 1 amp (pilot duty) @ 30 Vdc. The relay’s<br />

position is supervised to avoid accidentally jarring it out of position.<br />

The SIGA-RB can be operated as a control relay if programmed to<br />

do so at the control panel (EST3 V. 2 only). The relay base does not<br />

support the SIGA-LED Remote LED.<br />

Audible Base SIGA-AB4G - This base is designed for use where<br />

localized or group alarm signaling is required. When the detector<br />

senses an alarm condition, the audible base emits a local alarm<br />

signal. The optional SIGA-CRR Polarity Reversal Relay can be used<br />

for sounding to other audible bases on the same 24 Vdc circuit.<br />

Relay and Audible Bases operate as follows:<br />

SIGA-RB<br />

Relay Base<br />

- at system power-up or reset, the relay is de-energized<br />

- when a detector is installed in the base with the power on,<br />

the relay energizes for four seconds, then de-energizes<br />

- when a detector is removed from a base with the power on,<br />

the relay is de-energized<br />

SIGA-LED<br />

Remote LED<br />

- when the detector enters the alarm state, the relay is energized.<br />

Isolator Base SIGA-IB, SIGA-IB4 - This base includes a built-in line<br />

fault isolator for use on Class A circuits. A detector must be installed<br />

for it to operate. The isolator base does not support the SIGA-LED<br />

Remote LED.<br />

The isolator operates as follows:<br />

- a short on the line causes all isolators to open within 23 msec<br />

- at 10 msec intervals, beginning on one side of the Class A<br />

circuit nearest the loop controller, the isolators close to<br />

provide the next isolator down the line with power<br />

- if the isolator next to the short closes, it reopens within 10 msec.<br />

The process repeats beginning on the other side of the loop controller.<br />

Remote LED SIGA-LED - The remote LED connects to the SIGA-SB<br />

or SIGA-SB4 Standard Base only. It features a North American size<br />

1-gang plastic faceplate with a white finish and red alarm LED.<br />

SIGA-TS4 Trim Skirt - Supplied with 4 inch bases, it can also be<br />

ordered separately to use with the other bases to help hide surface<br />

imperfections not covered by the smaller bases.<br />

Warnings & Cautions<br />

This detector will not operate without electrical power. As fires frequently<br />

cause power interruption, we suggest you discuss further<br />

safeguards with your fire protection specialist.<br />

This detector will NOT sense fires that start in areas where smoke<br />

cannot reach the detector. <strong>Smoke</strong> from fires in walls, roofs, or on the<br />

opposite side of closed doors may not reach the detector.<br />

This detector can be operated in environments where brief air velocity<br />

gusts of up to 300 ft per minute (1.52 m/s) are allowed.<br />

Data Sheet 85001-0291 Issue 8<br />

Not to be used for installation purposes. Page of 4


GE<br />

Security<br />

U.S.<br />

T 888-378-2329<br />

F 866-503-3996<br />

Canada<br />

T 519 376 2430<br />

F 519 376 7258<br />

Asia<br />

T 852 2907 8108<br />

F 852 2142 5063<br />

Australia<br />

T 61 3 9259 4700<br />

F 61 3 9259 4799<br />

Europe<br />

T 32 2 725 11 20<br />

F 32 2 721 86 13<br />

Latin America<br />

T 305 593 4301<br />

F 305 593 4300<br />

www.gesecurity.com<br />

© 2006 General Electric Company<br />

All Rights Reserved<br />

Signature Series is a Trademark<br />

of GE Security.<br />

Specifications<br />

Sensing Element <strong>Ionization</strong> - 1.0 µC Americium 241<br />

Air Velocity Range<br />

0 to 75 ft/min (0 to 0.38 m/s), (See Warnings and Cautions)<br />

Storage and Operating Operating Temp: 32ºF to 120ºF (0ºC to 49ºC)<br />

Environment<br />

Storage Temp: -4ºF to 140ºF (-20ºC to 60ºC)<br />

Humidity: 0 to 93% RH, Non-Condensing<br />

Altitude: 6,000 ft (1,828 m) maximum<br />

Sensitivity Range<br />

ULI / ULC - 0.61% to 1.91% obscuration/foot<br />

User Selected Alarm<br />

Most Sensitive: 0.7%/ft.; More Sensitive: 1.0% /ft. Normal: 1.2% /ft.<br />

Sensitivity Settings<br />

Less Sensitive: 1.4% /ft.; Least Sensitive: 1.6% /ft.<br />

Pre-alarm Sensitivity<br />

5% increments, allowing up to 20 pre-alarm settings<br />

Operating Voltage<br />

15.2 to 19.95 Vdc (19 Vdc nominal)<br />

Operating Current<br />

Quiescent: 45µA @ 19 V; Alarm: 45µA @ 19 V Emergency Standalone<br />

Alarm Mode: 18mA Pulse Current: 100 µA (100 msec) During<br />

Communication: 9 mA maximum<br />

Construction & Finish High Impact Engineering Polymer - White<br />

Compatible Mounting Bases SIGA-SB Standard Base, SIGA-RB Relay Base, SIGA-IB Isolator Base,<br />

SIGA-AB4, SIGA-AB4G Audible Bases<br />

LED Operation<br />

On-board Green LED - Flashes when polled On-board Red LED<br />

- Flashes when in alarm Both LEDs - Glow steady when in alarm<br />

(stand-alone) Compatible Remote Red LED SIGA-LED Flashes when<br />

in alarm<br />

Compatibility<br />

Use With: SIGNATURE Loop Controller<br />

Address Requirements Uses one Device Address<br />

UL Listed Spacing<br />

30 ft<br />

Agency Listings<br />

UL, ULC, MEA, CSFM<br />

Ordering Information<br />

Catalog Description<br />

Ship Wt.<br />

Number<br />

lbs (kg)<br />

SIGA-IS <strong>Intelligent</strong> <strong>Ionization</strong> <strong>Detector</strong> - UL/ULC Listed 0.5 (.23)<br />

Accessories<br />

SIGA-SB <strong>Detector</strong> Mounting Base - Standard<br />

SIGA-SB4 4 inch <strong>Detector</strong> Mounting Base c/w SIGA-TS4 Trim Skirt<br />

SIGA-RB <strong>Detector</strong> Mounting Base w/Relay<br />

0.2 (.09)<br />

SIGA-RB4 4 inch <strong>Detector</strong> Mounting Base w/Relay c/w SIGA-TS4 Trim Skirt<br />

SIGA-IB <strong>Detector</strong> Mounting Base w/Fault Isolator<br />

SIGA-IB4 4 inch <strong>Detector</strong> Mounting Base w/Fault Isolator<br />

and SIGA-TS4 Trim Skirt<br />

0.1 (.04)<br />

SIGA-AB4G Audible (Sounder) Base 0.1 (.04)<br />

Data Sheet 85001-0291 Issue 8<br />

Not to be used for installation purposes. Page of 4

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!