Troubleshooting<br />

Error code Fault description<br />

Display<br />

Time exceeded – blowing cold<br />

Safety time exceeded<br />

Flame aborted from control stage<br />

“large”<br />

Flame aborted from control stage<br />

“small”<br />

Temperature sensor – interruption<br />

Please note<br />

The test with a bridge in the 14-pole<br />

connector can only be performed if<br />

HYDRONIC is still installed in the<br />

vehicle or if a test facility is available.<br />

Temperature sensor – short-circuit,<br />

overload or accidental ground<br />

Please note<br />

The test with a bridge in the 14-pole<br />

connector can only be performed if<br />

HYDRONIC is still installed in the<br />

vehicle or if a test facility is available.<br />

Explanations<br />

Remedies<br />

At start, flame sensor reports temperature > 70°C for longer<br />

than 240°C.<br />

Check exhaust and combustion air guidance.<br />

Check flame sensor – control values see page 34.<br />

Check exhaust and combustion air guidance.<br />

Check fuel quantity and fuel supply, see page 41.<br />

Clean or replace filter in dosing pump connection.<br />

Warning<br />

After flame aborted from control stage “large” or “small” and<br />

after starting attempt within allowed number, HYDRONIC<br />

proceeds with a new start, where applicable with subsequent<br />

start repeat.<br />

If the new start or start repeat is successful, the error code is<br />

deleted.<br />

Error (because no more starting attempts allowed)<br />

Check exhaust and combustion air guidance.<br />

Check fuel quantity and fuel supply, see page 41.<br />

Check flame sensor, see error code 064 and 065.<br />

Remove controller and check connection lead of temperature<br />

sensor for any signs of damage. If the lead is OK, then<br />

short the temperature sensor: route the cable in the 14-pole<br />

connector from chamber 3 to chamber 4.<br />

Switch HYDRONIC on:<br />

– If error code 061 appears, then remove and check<br />

temperature sensor, see page 38.<br />

– If error code 060 still appears, then check and if<br />

necessary replace controller.<br />

Remove controller and check connection lead of<br />

temperature sensor for any signs of damage. If the lead is<br />

OK, then remove the 14-pole connector from controller,<br />

unclip cable 0.5 2 blue from chamber 3 and cable 0.5 2 blue<br />

from chamber 4.<br />

Connect 14-pole connector to controller and switch<br />

HYDRONIC on.<br />

– If error code 061 appears, then remove and check<br />

temperature sensor, see page 38.<br />

– If error code 061 appears, then check and if necessary<br />

replace controller.