MODEL DPV-1 DRY PIPE V A LVE - Tyco Fire Products
MODEL DPV-1 DRY PIPE V A LVE - Tyco Fire Products
MODEL DPV-1 DRY PIPE V A LVE - Tyco Fire Products
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
FEATURES & BENEFITS<br />
◆ External Reset<br />
◆ 250 psi (17,2 bar) Pressure Rating<br />
◆ Unique Offset Single Clapper<br />
Design Enabling a Simple<br />
Compact Valve<br />
◆ Ductile Iron Construction to<br />
Ensure a Lightweight Valve<br />
◆ Simple Reset Procedure<br />
◆ No Priming Water Required<br />
◆ Compact, Semi-preassembled<br />
and Fully Assembled, and<br />
Easy to Operate Valve Trim<br />
AVAILABLE FULLY PRE-TRIMMED.<br />
GENERAL DESCRIPTION<br />
The Model <strong>DPV</strong>-1 Dry Pipe Valves are differential<br />
valves used to automatically control the<br />
flow of water into a dry pipe fire protection<br />
sprinkler system upon operation of one or more<br />
automatic sprinklers. The <strong>DPV</strong>-1 also provides<br />
for actuation of fire alarms upon system<br />
operation.<br />
Dry pipe sprinkler systems are used in unheated<br />
warehouses, parking garages, store windows,<br />
attic spaces, loading docks, and other areas<br />
exposed to freezing temperatures, where water<br />
filled pipe cannot be utilized. When set for<br />
service, the dry pipe sprinkler system is<br />
pressurized with air (or nitrogen). The loss of<br />
pressure through an operated automatic<br />
sprinkler in response to heat from a fire permits<br />
the <strong>DPV</strong>-1 Dry Pipe Valve to open and allow a<br />
flow of water into the sprinkler system piping.<br />
<strong>MODEL</strong> <strong>DPV</strong>-1 <strong>DRY</strong> <strong>PIPE</strong> V A <strong>LVE</strong><br />
External Resetting, 2-1/2 thru 6 inch, 250 psi<br />
4" <strong>DPV</strong>-1<br />
AVAILABLE END CONNECTIONS AND SIZES<br />
Nominal Valve Sizes<br />
End Connections 2-1/2" 3" 4" 6"<br />
(DN65) (DN80) (DN100) (DN150)<br />
FLANGE X FLANGE N/A N/A ◆ ◆<br />
77 lbs* 120 lbs*<br />
FLANGE X GROOVE N/A N/A ◆ ◆<br />
67 lbs* 108 lbs*<br />
GROOVE X GROOVE ◆ ◆ ◆ ◆<br />
37.5 lbs* 37.5 lbs* 57 lbs* 92 lbs*<br />
◆ Available N/A Not Available<br />
* Nominal weight of valve and trim combined.<br />
Always refer to the Technical Data Sheet TFP1020 for complete description of all Listing criteria, design<br />
parameters, installation instructions, care and maintenance guidelines, and our limited warranty.<br />
TYCO is a registered trademark of <strong>Tyco</strong> International Services GmbH, and is used under license by <strong>Tyco</strong> <strong>Fire</strong> & Building <strong>Products</strong> and its affiliates in the United States and other countries.<br />
2-1/2" & 3" <strong>DPV</strong>-1<br />
6" <strong>DPV</strong>-1
<strong>MODEL</strong> <strong>DPV</strong>-1 ORDERING PROCEDURE & SPECIFICATIONS<br />
Part Numbers indicate size and inlet/outlet connections<br />
VA<strong>LVE</strong> SIZE & CONNECTIONS<br />
2-1/2" (DN65)<br />
6-3/4"<br />
(170 mm)<br />
Groove x Groove<br />
P/N: 52-310-1-910<br />
3" (DN80)<br />
Groove x Groove<br />
P/N: 52-310-1-912<br />
4" (DN100)<br />
Groove x Groove<br />
P/N: 52-310-1-913<br />
Flange x Groove<br />
P/N: 52-310-1-413<br />
Flange x Flange<br />
P/N: 52-310-1-013<br />
6" (DN150)<br />
Groove x Groove<br />
P/N: 52-310-1-915<br />
Flange x Groove<br />
P/N: 52-310-1-415<br />
Flange x Flange<br />
P/N: 52-310-1-015<br />
1" NPT<br />
AIR SUPPLY<br />
PORT<br />
1/2" NPT<br />
WATER<br />
SUPPLY<br />
PRESSURE<br />
& ALARM<br />
TEST PORT<br />
AIR PRESSURE<br />
TO SYSTEM<br />
FROM<br />
WATER SUPPLY<br />
SET POSITION<br />
<strong>Tyco</strong> <strong>Fire</strong> & Building <strong>Products</strong><br />
Technical Services<br />
Phone: 800-381-9312<br />
Fax: 800-791-5500<br />
www.<strong>Tyco</strong>-<strong>Fire</strong>.com<br />
12"<br />
(300 mm)<br />
11-1/2"<br />
(290 mm)<br />
CLAPPER<br />
ASSEMBLY<br />
IN SET<br />
POSITION<br />
8"<br />
(200 mm)<br />
6"<br />
(150 mm)<br />
7-1/4"<br />
(190 mm)<br />
3/4" NPT ALARM<br />
PORT OPEN TO<br />
ATMOSPHERE<br />
16-9/16"<br />
(420,7 mm)<br />
6"<br />
(150 mm)<br />
17-1/4"<br />
(440 mm)<br />
2-1/2"<br />
(65 mm)<br />
18-3/4"<br />
(475 mm)<br />
4-1/2"<br />
(115 mm)<br />
12"<br />
(304,8 mm)<br />
2-1/2 or 3 INCH<br />
VA<strong>LVE</strong>S<br />
FxF: 13-5/8"<br />
(346,1 mm)<br />
FxG: 13-11/16"<br />
(347,7 mm)<br />
GxG: 13-3/4"<br />
(349,3 mm)<br />
CLAPPER<br />
ASSEMBLY<br />
FULLY OPEN<br />
CLAPPER LATCH<br />
PIVOTS TO ALLOW<br />
CLAPPER ASSEMBLY<br />
TO FULLY OPEN<br />
12"<br />
(305 mm)<br />
15"<br />
(380 mm)<br />
WATERFLOW<br />
TO SYSTEM<br />
12"<br />
(300 mm)<br />
FROM<br />
WATER SUPPLY<br />
OPERATED POSITION<br />
Always refer to the Technical Data Sheet TFP1020 for complete description of all Listing criteria, design<br />
parameters, installation instructions, care and maintenance guidelines, and our limited warranty.<br />
All brand names, product names or trademarks belong to their respective owners. <strong>Tyco</strong> <strong>Fire</strong> & Building <strong>Products</strong> reserves the right<br />
to change product design and specifications without notice. Copyright © 2007 <strong>Tyco</strong> <strong>Fire</strong> <strong>Products</strong> LP. All rights reserved.<br />
9-1/4"<br />
(235 mm)<br />
14-3/4"<br />
(375 mm)<br />
ALARM PORT<br />
WATERFLOW<br />
TO ALARM<br />
14"<br />
(355 mm)<br />
16"<br />
(406.4 mm)<br />
FxF, FxG,<br />
or GxG<br />
Model <strong>DPV</strong>-1 Dry Pipe Valves Set and Open Positions<br />
CLAPPER LATCH<br />
PIVOTS TO UNLATCH<br />
CLAPPER ASSEMBLY<br />
WEIGHT<br />
The following are the nominal<br />
weights for the valve and trim:<br />
2-1/2" Model <strong>DPV</strong>-1<br />
Groove x Groove 37.5 lbs.<br />
3" Model <strong>DPV</strong>-1<br />
Groove x Groove 37.5 lbs.<br />
4" Model <strong>DPV</strong>-1<br />
Groove x Groove 57 lbs.<br />
Flange x Groove 67 lbs.<br />
Flange x Flange 72 lbs.<br />
6" Model <strong>DPV</strong>-1<br />
Groove x Groove 92 lbs.<br />
Flange x Groove 108 lbs.<br />
Flange x Flange 120 lbs.<br />
OPTIONAL ACCELERATORS<br />
Model QRS<br />
Electronic Accelerator<br />
(Details provided in TFP1100)<br />
Specify: Model QRS<br />
Electronic Dry Pipe<br />
Accelerator Package<br />
P/N 52-312-2-102<br />
Model ACC-1<br />
Mechanical Accelerator<br />
(Details provided in TFP1112)<br />
Specify : Model ACC-1<br />
Mechanical Dry Pipe<br />
Accelerator Package<br />
P/N 52-311-1-001<br />
DRAIN FROM<br />
SYSTEM COMPLETE<br />
WATER SUPPLY<br />
SHUT OFF<br />
RESET POSITION<br />
PUSH HERE<br />
TO RESET<br />
VA<strong>LVE</strong><br />
RESET<br />
KNOB<br />
CLAPPER<br />
ASSEMBLY<br />
RESEATED<br />
Printed in USA / PP / 5M / TF-2007026 04-07